Aquavar Intelligent Pump Controller

CentriPro

Warning/Alarm

Description

Cause

Remedy

24 — External fan fault

The fan warning function checks if the 

fan is running. The fan warning can be 

disabled on [14– 53] Fan Monitor.

Check for proper fan operation. 
Cycle power to the frequency 

converter and check that the fan 

operates briefly at startup.
Check the sensors on the heatsink 

and control card.

25 — Brake resistor short 

circuit

The brake resistor is monitored during 

operation. If a short circuit occurs, 

the brake function is disabled and 

the warning appears. The frequency 

converter is still operational but 

without the brake function.

Remove power to the frequency 

converter and replace the brake 

resistor (see [2–15] Brake Check).

26 — Brake resistor power 

limit

The power transmitted to the brake 

resistor is calculated as a mean value 

over the last 120 seconds of run 

time. The calculation is based on the 

intermediate circuit voltage and the 

brake resistance value set in [2–16] 

brake Max. Current.

The warning is active when the 

dissipated braking is higher 

than 90% of the brake resistance 

power.
If Trip [2] is selected in [2–13] 

Brake Power Monitoring, the 

frequency converter will trip 

when the dissipated braking 

power reaches 100%.

27 — Brake chopper fault

The brake transistor is monitored 

during operation and if a short circuit 

occurs, the brake function is disabled 

and a warning is issued.

The frequency converter is still 

operational but, since the brake 

transistor has short-circuited, 

substantial power is transmitted 

to the brake resistor, even if it is 

inactive.

Remove power to the frequency 

converter and remove the brake 

resistor.

28 — Brake check failed

The brake resistor is not connected or 

not working.

Check [2–15] Brake Check.

29 — Heatsink temp

The maximum temperature of the 

heatsink has been exceeded. The 

temperature fault will not reset until 

the temperature falls below the 

reset heatsink temperature. The trip 

and reset points are based on the 

frequency converter power size.

Check for the following conditions:
• Ambient temperature too high.
• Motor cable too long.
• Incorrect airflow clearance above 

and below the frequency converter.

• Blocked airflow around the 

frequency converter.

• Damaged heatsink fan.
• Dirty heatsink.

30 — Motor phase U 

missing

Motor phase U between the frequency 

converter and the motor is missing.

Remove power from the frequency 

converter and check motor phase U.

31 — Motor phase V 

missing

Motor phase V between the frequency 

converter and the motor is missing.

Remove power from the frequency 

converter and check motor phase V.

32 — Motor phase W 

missing

Motor phase W between the frequency 

converter and the motor is missing.

Remove power from the frequency 

converter and check motor phase W.

33 — Inrush fault

Too many power-ups have occurred 

within a short time period.

Let the unit cool to operating 

temperature.

34 — Fieldbus 

communication fault

Communication between the fieldbus 

and the communication option card is 

not operating.

Summary of Contents for Aquavar IPC

Page 1: ...Aquavar IPC WARNINGS AND ALARMS DOCUMENT INSTRUCTION MANUAL IM299...

Page 2: ...ears for a fault in the input rectifier on the frequency converter Options are programmed at 14 12 Function at Input Imbalance not applicable for single phase drives Check the supply voltage and suppl...

Page 3: ...tor Current is correct 11 Motor thermistor over temp The thermistor might be disconnected Select whether the frequency converter gives a warning or an alarm in 1 90 Motor Thermal Protection Check for...

Page 4: ...0 FC Type 15 41 Power Section 15 42 Voltage 15 43 Software Version 15 45 Actual Typecode String 15 49 SW ID Control Card 15 50 SW ID Power Cord 15 60 Option Mounted 15 61 Option SW Version 16 Short ci...

Page 5: ...ing is issued The frequency converter is still operational but since the brake transistor has short circuited substantial power is transmitted to the brake resistor even if it is inactive Remove power...

Page 6: ...rd The problem could be on the power card on the gate drive card or the ribbon cable between the power card and gate drive card 40 Overload of digital output terminal 27 Check the load connected to te...

Page 7: ...r Speed High Limit RPM the frequency converter will show a warning When the speed is below the specified limit in 1 86 Trip Speed Low RPM except when starting or stopping the frequency converter will...

Page 8: ...ower card temperature The temperature sensor on the power card is either too hot or too cold Check that the ambient operating temperature is within limits Check for clogged filters Check fan operation...

Page 9: ...ller had entered fire mode Cycle power to the unit to remove the warning See the fire mode data in the alarm log on the controller 202 Fire mode limits exceeded While operating in fire mode one or mor...

Page 10: ...shorts or incorrect connections If the display continues to cut out follow the procedure for display dark Motor not running Service switch open or missing motor connection Check if the motor is connec...

Page 11: ...ck brake parameters Check ramp time settings Check parameter group 2 0 DC Brake and 3 0 Reference Limits Open power fuses or circuit breaker trip Phase to phase short Motor or panel has a short phase...

Page 12: ...e makes noise or vibrations at certain frequencies Resonances for example in the motor pump system Bypass critical frequencies by using parameters in parameter group 4 6 Speed Bypass Check if noise an...

Reviews: