Xylem Aquavar IPC Instruction Manual Download Page 7

PAGE 7

Aquavar Intelligent Pump Controller

CentriPro

Warning/Alarm

Description

Cause

Remedy

46 — Power card supply

The supply on the power card is out of 

range.

There are three power supplies 

generated by the switch mode 

power supply (SMPS) on the 

power card: 24 V, 5 V, +/- 18 V. 

When powered with 24 VDC with 

the 24VDC Backup Option Card 

option, only the 24 V and 5 V 

supplies are monitored. When 

powered with three-phase mains 

voltage, all three supplied are 

monitored.

Check for a defective power cord.
Check for a defective control card.
Check for a defective option card. 
If a 24 VDC power supply is used, 

verify proper supply power.

47 — 24 V supply low

The 24 V DC is measured on the 

control card.

The external 24 V DC backup 

power supply may be overloaded.

Contact your Xylem supplier.

48 — 1.8 V supply low

The power supply is measured on the 

control card.

The 1.8 V DC supply used on 

the control card is outside of 

allowable limits.

Check for a defective control card.
If an option card is present, check for 

an overvoltage condition.

49 — Speed limit

When the speed is not within the 

specified range in [4–11] Motor Speed 

Low Limit [RPM] and [4–13] Motor 

Speed High Limit [RPM], the frequency 

converter will show a warning.

When the speed is below the 

specified limit in [1–86] Trip 

Speed Low [RPM] (except 

when starting or stopping) the 

frequency converter will trip.

50 — AMA calibration failed

Contact your Xylem supplier or Xylem 

Service Department.

51 — AMA check Unom and 

Inom

The settings for motor voltage, motor 

current, and motor power are wrong.

Check the settings in parameters 

1–20 to 1–25.

52 — AMA low Inom

The motor current is too low. 

Check the setting in [4–18] Current 

Limit.

53 — AMA motor too big

The motor is too big for the AMA to 

operate.

54 — AMA motor too small

The motor is too small for the AMA to 

operate.

55 — AMA Parameter out 

of range

The parameter values of the motor are 

outside of the acceptable range. AMA 

will not run.

56 — AMA interrupted by 

the user

The AMA has been interrupted by the 

user.

57 — AMA timeout

Try to restart AMA again. Repeated 

restarts may overheat the motor.

58 — AMA internal fault

Contact your Xylem supplier.

59 — Current limit

The current is higher than the value in 

[4–18] Current Limit.

Ensure that motor data in parameters 

1–20 through 1–25 are set correctly.
Possibly increase the current limit. 

Be sure that the system can operate 

safely at a higher limit.

60 — Pump Protect

A digital input signal is indicating 

a pump protection external to the 

controller is active.

Summary of Contents for Aquavar IPC

Page 1: ...Aquavar IPC WARNINGS AND ALARMS DOCUMENT INSTRUCTION MANUAL IM299...

Page 2: ...ears for a fault in the input rectifier on the frequency converter Options are programmed at 14 12 Function at Input Imbalance not applicable for single phase drives Check the supply voltage and suppl...

Page 3: ...tor Current is correct 11 Motor thermistor over temp The thermistor might be disconnected Select whether the frequency converter gives a warning or an alarm in 1 90 Motor Thermal Protection Check for...

Page 4: ...0 FC Type 15 41 Power Section 15 42 Voltage 15 43 Software Version 15 45 Actual Typecode String 15 49 SW ID Control Card 15 50 SW ID Power Cord 15 60 Option Mounted 15 61 Option SW Version 16 Short ci...

Page 5: ...ing is issued The frequency converter is still operational but since the brake transistor has short circuited substantial power is transmitted to the brake resistor even if it is inactive Remove power...

Page 6: ...rd The problem could be on the power card on the gate drive card or the ribbon cable between the power card and gate drive card 40 Overload of digital output terminal 27 Check the load connected to te...

Page 7: ...r Speed High Limit RPM the frequency converter will show a warning When the speed is below the specified limit in 1 86 Trip Speed Low RPM except when starting or stopping the frequency converter will...

Page 8: ...ower card temperature The temperature sensor on the power card is either too hot or too cold Check that the ambient operating temperature is within limits Check for clogged filters Check fan operation...

Page 9: ...ller had entered fire mode Cycle power to the unit to remove the warning See the fire mode data in the alarm log on the controller 202 Fire mode limits exceeded While operating in fire mode one or mor...

Page 10: ...shorts or incorrect connections If the display continues to cut out follow the procedure for display dark Motor not running Service switch open or missing motor connection Check if the motor is connec...

Page 11: ...ck brake parameters Check ramp time settings Check parameter group 2 0 DC Brake and 3 0 Reference Limits Open power fuses or circuit breaker trip Phase to phase short Motor or panel has a short phase...

Page 12: ...e makes noise or vibrations at certain frequencies Resonances for example in the motor pump system Bypass critical frequencies by using parameters in parameter group 4 6 Speed Bypass Check if noise an...

Reviews: