PAGE 8

Aquavar Intelligent Pump Controller

CentriPro

Warning/Alarm

Description

Cause

Remedy

62 — Output frequency at 

maximum limit

The output frequency has reached 

the value set in [4–19] Max Output 

Frequency.

Check the application to determine 

the cause. Possibly increase the 

output frequency. Be sure the system 

can operate safely at a higher output 

frequency. The warning will clear 

wieh the output drops below the 

maximum limit.

65 — Control card over 

temperature

The cut-out temperature of the control 

card is 80°C.

Check that the ambient operating 

temperature is within limits.
Check for clogged filters.
Check fan operation. 
Check the control card.

66 — Heatsink temperature 

low

The frequency converter is too cold 

to operate. This warning is based on 

the temperature sensor in the IGBT 

module.

Increase the ambient temperature of 

the unit.
A trickle amount of current can be 

supplied to the frequency controller 

whenever the motor is stopped by 

setting [2–00] DC Hold/Preheat 

Current at 5% and [1–80] Function 

at Stop.

67 — Option module 

configuration has changed

One or more options have either been 

added or removed since the last power 

down.

Check that the configuration change 

is intentional and reset the frequency 

controller.

68 — Safe stop activated

Loss of the 24 VDC signal on terminal 

37 has caused the frequency controller 

to trip.

To resume normal operation, apply 

24 VDC to terminal 37 and reset the 

frequency controller.

69 — Power card 

temperature

The temperature sensor on the power 

card is either too hot or too cold.

Check that the ambient operating 

temperature is within limits.
Check for clogged filters.
Check fan operation.
Check the power card.

70 — Illegal FC 

configuration

The control card and power card are 

incompatible.

Contact your supplier with the 

typecode of the unit from the

80 — Drive initialized to 

default value

Parameter settings are initialized to 

default settings after a manual reset.

Reset the unit to clear the alarm.

92 — No flow

A no-flow condition has been detected 

in the system.

[22–23] No-Flow Function is set 

for alarm.

Troubleshoot the system and reset 

the frequency converter after the fault 

has been cleared.

93 — No Water/Loss of 

Prime

A low power condition in the system 

with the frequency converter operating 

at high speed may indicate a the pump 

is out of water or has lost prime.

[22–26] No Water/Loss of Prime 

Function is set for alarm. The [22– 

39] No Water/Loss of Prime Limit 

is set too high.

Troubleshoot the system and reset 

the frequency converter after the fault 

has been cleared.

94 — Under Pressure

The system pressure is below the 

Under Pressure limit (Under Pressure 

Limit = Setpoint [22–25] Under 

Pressure Difference).

This may indicate leakage in the 

system. [22–50] Under Pressure 

Function is set for alarm.

Troubleshoot the system, and reset 

the frequency converter after the fault 

has been cleared.

95 — Broken belt

Torque is below the torque level set for 

no load, indicating a broken belt.

[22–60] Broken Belt Function is 

set for alarm.

Troubleshoot the system and reset 

the frequency converter after the fault 

has been cleared.

Summary of Contents for Aquavar IPC

Page 1: ...Aquavar IPC WARNINGS AND ALARMS DOCUMENT INSTRUCTION MANUAL IM299...

Page 2: ...ears for a fault in the input rectifier on the frequency converter Options are programmed at 14 12 Function at Input Imbalance not applicable for single phase drives Check the supply voltage and suppl...

Page 3: ...tor Current is correct 11 Motor thermistor over temp The thermistor might be disconnected Select whether the frequency converter gives a warning or an alarm in 1 90 Motor Thermal Protection Check for...

Page 4: ...0 FC Type 15 41 Power Section 15 42 Voltage 15 43 Software Version 15 45 Actual Typecode String 15 49 SW ID Control Card 15 50 SW ID Power Cord 15 60 Option Mounted 15 61 Option SW Version 16 Short ci...

Page 5: ...ing is issued The frequency converter is still operational but since the brake transistor has short circuited substantial power is transmitted to the brake resistor even if it is inactive Remove power...

Page 6: ...rd The problem could be on the power card on the gate drive card or the ribbon cable between the power card and gate drive card 40 Overload of digital output terminal 27 Check the load connected to te...

Page 7: ...r Speed High Limit RPM the frequency converter will show a warning When the speed is below the specified limit in 1 86 Trip Speed Low RPM except when starting or stopping the frequency converter will...

Page 8: ...ower card temperature The temperature sensor on the power card is either too hot or too cold Check that the ambient operating temperature is within limits Check for clogged filters Check fan operation...

Page 9: ...ller had entered fire mode Cycle power to the unit to remove the warning See the fire mode data in the alarm log on the controller 202 Fire mode limits exceeded While operating in fire mode one or mor...

Page 10: ...shorts or incorrect connections If the display continues to cut out follow the procedure for display dark Motor not running Service switch open or missing motor connection Check if the motor is connec...

Page 11: ...ck brake parameters Check ramp time settings Check parameter group 2 0 DC Brake and 3 0 Reference Limits Open power fuses or circuit breaker trip Phase to phase short Motor or panel has a short phase...

Page 12: ...e makes noise or vibrations at certain frequencies Resonances for example in the motor pump system Bypass critical frequencies by using parameters in parameter group 4 6 Speed Bypass Check if noise an...

Reviews: