Storage Temperature 

Recharge Frequency 

Charging Duration 

-25°C - 40°C 

Every 3 months 

1-2 hours 

40°C - 45°C 

Every 2 months 

1-2 hours 

 

 
 

Symptom

 

Possible cause

 

Remedy

 

Fault code is shown as 14 on LCD 
display and alarm is continuously 
sounding. 

The UPS shut down 
automatically because short 
circuit occurs on the UPS 
output. 

Check  output  wiring  and  if 
connected    devices    are    in 
short circuit status. 

Fault code is shown as 01, 02, 03, 
11, 12, 13 and 41 on LCD display and 
alarm is continuously sounding. 

A    UPS    internal    fault    has 
occurred.  There  are  two 
possible results: 
1. The load is still supplied, 
but directly from AC power 
via bypass. 
2.   The   load   is   no   longer 
supplied by power. 

Contact your dealer 

Battery backup time is shorter than 
nominal value. 

Batteries are not fully 
charged 

Charge the batteries for at 
least 5 hours and then check 
capacity. If the problem still 
persists, consult your dealer. 

Batteries defect 

Contact your dealer to 
replace the battery. 

Fault code is shown as 2A on LCD 
display and alarm is continuously 
sounding. 

The short circuit occurs on 
the charger output. 

Check if battery wiring of 
connected external pack is in 
short circuit status. 

Fault code is shown as 45 on LCD 
display. At the same time, alarm is 
continuously sounding. 

The  charger  does  not  have 
output and battery voltage is 
less than 10V/PC. 

Contact your dealer. 

 

 

5. Storage and Maintenance

 

Operation

 

 

The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C 
ambient  temperature) has  been  exceeded, the batteries  must  be  replaced.  In  this  case,  please 
contact your dealer. 

 

 
 

 

Be sure to deliver the spent battery to a recycling facility or ship it to your 

dealer in the replacement battery packing material. 

 

 

Storage

 

 

Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry location. 

During storage, recharge the battery in accordance with the following table: 

Summary of Contents for P91g Series

Page 1: ...P91 P91g Lead Acid Online UPS 1000VA 2000VA 3000VA Models User Installation Manual www xpcc com 2021 Xtreme Power Conversion Corporation All rights reserved Rev 10 21 21...

Page 2: ...Setup the UPS 7 2 5 Battery Replacement 11 2 6 Battery Kit Assembly 12 3 Operations 15 3 1 Button operation 15 3 2 LCD Panel 15 3 3 Audible Alarm 16 3 4 LCD display wordings index 17 3 5 UPS Setting...

Page 3: ...Place cables in such a way that no one can step on or trip over them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no pr...

Page 4: ...ify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS capacitors To avoid electrical shock turn off the unit and unplug it form the A...

Page 5: ...to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment i...

Page 6: ...ure that nothing inside the package is damaged Please keep the original package in a safe place for future use 2 1 Rear panel view P91g models 1500 Model 2000 Model 3000 Model P91 models 1000 1500 Mod...

Page 7: ...ptible Power Supply Xtreme Power Conversion Corporation Page 5 5 USB communication port 6 RS 232 communication port 7 SNMP intelligent slot 8 Emergency power off function connector EPO 9 External batt...

Page 8: ...Rectifier PFC Dynamic Bypass Inverter Battery Charger The UPS is composed of mains input EMI RFI filters rectifier PFC inverter battery charger DC to DC converter battery dynamic bypass and UPS output...

Page 9: ...clearance of 100mm in the bottom of the UPS to avoid dust and high temperature 2 Place UPS It s equipped with fan for cooling Therefore place the UPS in a well ventilated area It s required to mainta...

Page 10: ...ttery pack s Note If you have multiple battery packs available connect them serially An example is shown in the diagram below connecting the second battery connector of the first battery pack to the f...

Page 11: ...onnection There are two kinds of outputs programmable outlets and general outlets Please connect non critical devices to the programmable outlets and critical devices to the general outlets During pow...

Page 12: ...able EPO function This UPS is equipped with EPO function By default the UPS is delivered from factory with Pin 1 and pin 2 closed a metal plate is connected to Pin 1 and Pin2 for UPS normal operation...

Page 13: ...er restarts the monitoring software will appear as an orange plug icon located in the system tray near the clock 2 5 Battery Replacement When the icons of and are flashing in LCD display and alarm is...

Page 14: ...connect the battery wires Put the front panel back to the unit 2 6 Battery Kit Assembly NOTICE Please assemble battery kit first before installing it inside of UPS Please select correct battery kit p...

Page 15: ...embled battery packs on one side of plastic shells as below chart Step 4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 4 battery kit Step 1 Remove adhesive tap...

Page 16: ...ation Page 14 6 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Tapes Tapes Step 3 Put assembled battery packs on one side of plastic shells Step...

Page 17: ...g this button Confirm selection key Press this button to confirm selection in UPS setting mode Select Button Switch LCD message Press this button to change the LCD message for input voltage input freq...

Page 18: ...frequency load current and load percent k kilo W watt V voltage A ampere percent centigrade degree Hz frequency Load information Indicates the load level by 0 24 25 49 50 74 and 75 100 Indicates overl...

Page 19: ...ngs index Abbreviation Display content Meaning ENA Enable DIS Disable ESC Escape HLS High loss LLS Low loss AO Active open AC Active close EAT Estimated autonomy time RAT Running autonomy time SD Shut...

Page 20: ...Vac For P91 models you may choose the following output voltage 100 presents output voltage is 100Vac 110 presents output voltage is 110Vac 115 presents output voltage is 115Vac 120 presents output vol...

Page 21: ...ting range in parameter 3 is from 7V to 24V of the nominal voltage Default 12V For P91 models the setting voltage in parameter 3 is from 3V to 12V of the nominal voltage Default 6V 06 Bypass enable di...

Page 22: ...els 55 59Hz setting the frequency low loss point from 55Hz to 59Hz Default 57 0Hz 09 Programmable outlets enable disable Interface Setting Parameter 2 Enable or disable programmable outlets ENA Progra...

Page 23: ...ty as following table for reference Battery capacity AH Total charging current A 7 20 2 20 40 4 40 60 6 60 8 14 Charger boost voltage setting Interface Setting Parameter 2 Set up the charger boost vol...

Page 24: ...ing mode Description LCD display Online mode When the input voltage is within acceptable range UPS will provide pure and stable AC power to output The UPS will also charge the battery in online mode E...

Page 25: ...4 x Over input current 49 x 3 8 Warning indicator Warning Icon flashing Code Alarm Low Battery Sounding every 2 seconds Overload Sounding every second Over input current Sounding 2 beep every 10 secon...

Page 26: ...ttery is incorrectly connected Check if all batteries are connected well Fault code is shown as 27 on LCD display and alarm is continuously sounding Battery voltage is too high or the charger is fault...

Page 27: ...r at least 5 hours and then check capacity If the problem still persists consult your dealer Batteries defect Contact your dealer to replace the battery Fault code is shown as 2A on LCD display and al...

Page 28: ...are horizontal brackets tower pedestals user manual AVAILABLE OPTIONS Bypass distribution XBDM power distribution XPDU 4 post rail kit 2 post shelf kit wall mount bracket Depending on load level P91g...

Page 29: ...930W 16A 125Vac input 2000VA 1850W 16 7A 120Vac input 2000VA 1740W 17 4A 115Vac input 2000VA 1640W 18 2A 110Vac input 1800VA 1500W 18A 100Vac input P91 3000 100 125Vac 50 60Hz 24A 1 100 110 115 120 12...

Page 30: ...P90 BP72 Used with UPS Models P91 1500 P91g 1500 P91 2000 P91g 2000 P91 3000 P91g 3000 Battery Type 12V 9Ah 12V 9Ah 12V 9Ah 12V 9Ah Battery Numbers 6 12 8 12 Dimensions WxDxH 17 2 x 18 9 x 3 5 in 17...

Page 31: ...echnician will ask you for the above information and if possible help solve your problem over the phone In the event that the unit requires factory service the technician will issue you a Return Mater...

Page 32: ...the equipment is repaired or modified by anyone other than XPC Corporation or a XPC Corporation approved third party b the equipment is damaged by the customer is improperly used or stored is subjecte...

Page 33: ...r d the total amount of all payment s you have or are entitled to receive from insurance other warranties extended warranties a legal liability claim or from other sources or persons for the damaged C...

Page 34: ...vice may be connected to the output sockets of the Product The installation must comply with all applicable electrical and safety codes set forth pursuant to the NEC 4 The Product must have undeniable...

Page 35: ...ILITY OF SUCH DAMAGE SUCH DAMAGES INCLUDE BUT ARE NOT LIMITED TO LOSS OF PROFITS LOSS OF SAVINGS OR REVENUE LOSS OF USE OF THE PRODUCT OR THE CONNECTED EQUIPMENT OR ANY ASSOCIATED EQUIPMENT LOSS OF SO...

Page 36: ...nt to XPC if it chooses to reimburse the Purchaser for the fair market value of the Connected Equipment XPCs maximum liability shall be reduced to reflect all such other payments or sources of recover...

Reviews: