background image

Xtralis ICAM 

Xtralis ICAM ILS-1 Product Guide

6.3.2 Flow Delays 

When airflow limits are exceeded, a Flow Fault will appear after a programmable Flow Delay time. The 
default Flow Delay time is approximately 30 seconds. Once the airflow is returned to a normal level, the 
fault condition will be cleared within 18 seconds. Available settings for Flow Delay are shown in Table 6-
2. 

In environments where the sampled airflow may be affected by sudden temperature or pressure 
changes or if there is a risk of physical interference of the sampling point (e.g. prison cell applications) 
then it may be necessary to increase the Flow Delay time. 

Table 6-2:  Flow Delay Settings 

Bargraph 
LED 

Flow into Fault 
Delay (Seconds) 

Flow out of Fault 
(Seconds) 

0 15 

1 30 

18 

2 60 

18 

3 90 

18 

4 120 

18 

5 150 

18 

6 180 

18 

7 210 

18 

8 240 

18 

9 270 

18 

Note:  

Timings are approximate. 

Note:  

The default flow delay setting is 1. 

6.3.3 Flow Sensitivity 

This setting determines the units responsiveness in reporting blocked sampling points or broken pipes. 

The default flow sensitivity value of 9 will configure the unit to declare a flow fault whenever there has 
been a change in volumetric airflow of ± 20% from the calibrated reading for at least the duration of the 
flow delay, see Section 6.3.2. For most installations, especially if compliance with EN54-20 is required, 
the default setting should be used. 

In certain circumstances, such as rapid changes in ambient air pressures due to air handling units, 
doors opening/closing etc. the default setting may appear to be too sensitive. Under these conditions, 
the flow delay setting should be increased to allow time for the air pressures to stabilize after the 
temporary event. 

Only under extreme environmental conditions or non standard pipe configurations should decreasing 
the flow sensitivity be considered. 

www.xtralis.com 

13

Summary of Contents for Xtralis ICAM ILS-1

Page 1: ...Xtralis ICAM ILS 1 Product Guide January 2009 Document Number 16277_00 Part Number 09 0113 10 ...

Page 2: ......

Page 3: ...Xtralis is not responsible and cannot be held accountable for any liability that may arise due to improper use of the equipment and or failure to take proper precautions Only persons trained through an Xtralis accredited training course can install test and maintain the system Liability You agree to install configure and use the products strictly in accordance with the User Manual and product docu...

Page 4: ...ription Caution This icon is used to indicate that there is a danger to equipment The danger could be loss of data physical damage or permanent corruption of configuration details Warning This icon is used to indicate that there is a danger of electric shock This may lead to death or permanent injury Warning This icon is used to indicate that there is a danger of inhaling dangerous substances This...

Page 5: ...Pipe Specification 5 4 2 Fixings 5 4 3 Bends 5 4 4 End Cap 6 4 5 Holes 6 4 6 Exhaust 6 4 7 Filters 6 4 8 Standard Pipe Configurations 6 5 Detectors 8 6 Setup 9 6 1 Display Functions 9 6 2 User Functions 10 6 3 Setup Notes 12 7 Testing 14 7 1 Detectors 14 7 2 System 14 8 Maintenance 15 9 EN54 20 Sensitivity Classes 16 10 Problem Solving 17 11 Specifications 18 www xtralis com iii ...

Page 6: ......

Page 7: ...f airflow can be displayed on a ten element bargraph with adjustments for high and low flow thresholds All detector configuration can be achieved with the integrated programming keys located on the side of the device The ILS 1 is a standalone system where faults and alarms are reported via separate volt free contacts These contacts may be connected to a monitoring fire alarm control panel Importan...

Page 8: ...egulations Remove the transparent cover using the special tool provided to unscrew the tamper proof fasteners Use the template provided to accurately position the holes then secure the unit to a suitable surface wall or ceiling through the four corner fixing points Ensure that the correct fasteners are used for the type of surface that the unit is mounted on 2 www xtralis com ...

Page 9: ...in access to the main circuit board for connection of the wiring remove the display detector mounting board held in place by the clear top cover Care should be taken when removing the board to ensure that the ribbon cable on the underside is not strained The ribbon cable may be removed from the connector on the underside of the board to allow the board to be fully removed To prevent risk of electr...

Page 10: ...nge state when the alarm level for the channel has been exceeded The terminals provide for Normally Open NO or Normally Closed NC operation 3 1 4 FAULT 2 Relay Contacts In the event of a fault condition the Fault relay will change state The terminals provide for Normally Open NO or Normally Closed NC operation Note NO NC refers to the un powered state of the relays Under normal non fault condition...

Page 11: ...s and the end cap hole 4 1 Pipe Specification For EN54 20 compliance the pipe should be Red ABS to EN 50086 1 Crush 1 Impact 1 Temp 31 with a nominal outer diameter of 25 mm or The sampling pipe is normally supplied in 3 m lengths and is cut as required and joined by solvent welded sockets permanent or socket unions removable Note The ILS 1 inlet port is tapered to allow a push fit of the sampling...

Page 12: ... reduce noise reduce risk of interference deliberate obstruction improved environmental protection etc Pipe of the same specification as the sampling pipe runs should be used and its length limited to a maximum of 10 m to avoid significant reduction in the air flow Care should be taken to position the new exhaust outlet where it cannot be accidentally or deliberately blocked 4 7 Filters Figure 4 3...

Page 13: ... 2 Double Pipe Tee Configuration Figure 4 5 Double pipe tee configuration The double pipe configuration can have a maximum length of 200 m 100 m per branch with up to 9 x 3 mm sampling holes and a 6 mm end hole per branch The distance from the unit to Tee should be at most 1 m and pipes should be balanced with equal lengths and equal number of holes See Section 9 EN54 20 Sensitivity Classes for de...

Page 14: ...1 processor Figure 5 1 Address switches for an ILS 1 system Each detector is identified with a two digit address which is set on switches on the underside of the top detector part The addresses should be left to the factory pre set values of 1 for the default detector in the channel detector 1 position and address 2 for the optional second detector in the channel detector 2 position Note If the de...

Page 15: ... FIRE Alarm BARGRAPH of Smoke level or Airflow speed SMOKE DETECTOR FAULT 1 per detector ISOLATE AIRFLOW OK HIGH AIRFLOW LOW AIRFLOW POWER ON FAN FAULT GENERAL FAULT RESET MAINS FAILURE Mains PSU Option Only UNLOCK BATTERY LOW Mains PSU Option Only CODE ENTRY DETECTOR OPERATING MODE www xtralis com 9 ...

Page 16: ...ase CHANGE key to modify setting The relevant LED flashes continuously to indicate the function selected To enable updates to the system enter the three digit access code 510 To enter numbers into the system each number must be sequentially selected in turn For example to select 5 press the CHANGE key six times to illuminate the number 5 LED on the display then press the SELECT button During this ...

Page 17: ...for Bargraph values 5 to 9 Select the BARGRAPH LED segment below which the FLOW LOW LED will be illuminated FLOW LOW flashes Low flow threshold can be set for Bargraph values 0 to 4 Set FLOW DELAY time of both channels FLOW HIGH and FLOW LOW LEDs both flash Please see Section 6 3 2 for information on flow delays Set smoke detector ALERT alarm threshold ALERT LED flashes Please refer to Table 9 1 S...

Page 18: ...tions when the pre set thresholds are exceeded on either detector This mode allows for continued operation in the event of a problem with one of the detectors Mode 3 1 AND 2 Two detectors working together Double Knock The display shows the lower of the two detector readings and the unit reports Alert Action and Fire conditions when the pre set thresholds are exceeded on BOTH detectors Note Mode 3 ...

Page 19: ...8 Note Timings are approximate Note The default flow delay setting is 1 6 3 3 Flow Sensitivity This setting determines the units responsiveness in reporting blocked sampling points or broken pipes The default flow sensitivity value of 9 will configure the unit to declare a flow fault whenever there has been a change in volumetric airflow of 20 from the calibrated reading for at least the duration ...

Page 20: ...m This test electronically simulates the effect of smoke in the sensing chamber 7 2 System The installed system must be checked with the top cover securely fitted As a minimum smoke should be introduced to the furthest sampling point from the ILS 1 unit on each branch of the pipe The choice of smoke source is dependant on the installation but in all cases the smoke must be present for the duration...

Page 21: ...ioned flush with the top of the filter tube 5 Remove the detector s from their mounting base s by twisting anti clockwise 6 Remove the detector cover by prying away the four side tabs with a small bladed screwdriver and then pulling the cover from the base 7 Vacuum the screen carefully without removing it If further cleaning is required continue with Step 8 otherwise skip to Step 12 8 Remove the s...

Page 22: ... A 100 4 1 N A N A 100 5 or above N A N A N A N A Note Table 9 1 shows the limits that should not be exceeded for the three sensitivity classes Figures are based upon the configurations shown in Section 4 8 Standard Pipe Configurations Maximum hole limits are based upon the following standard test configurations Class A 3 x 4 mm holes including 1 in end cap Class B 6 x 4 mm holes including 1 in en...

Page 23: ...please refer to Section 6 2 Ensure that filters are clean Section 8 Flow reading on Bargraph display moves erratically Decrease Flow sensitivity setting and re calibrate air flows Section 6 2 Flow reading unresponsive to broken or blocked pipes Increase Flow sensitivity setting and re calibrate air flows Section 6 2 Smoke Detector Fault indicated Ensure that correct address has been set Section 5 ...

Page 24: ...ength 100 m 100 m in Tee Configuration Environmental Protection IP65 with exhaust fitted IP23 without Operating Temperature 10 to 50ºC Operating Humidity 10 to 95 RH non condensing Approvals EN54 20 by VdS G206066 CE Certification EN61000 6 3 2001 A11 2004 EMC EN60950 1 2006 Safety CPD 89 106 EEC Table 11 2 Typical Current Consumption vs Fan Speed Bargraph Value 0 1 2 3 4 5 6 7 8 9 Fan Speed 1 2 3...

Reviews: