11 Specifications
Table 11-1: General ILS-1 Specifications
Number of Detectors
1 or 2, Laser based Analog Addressable
Filtration
Single stage dust particle filter
Flow Monitoring
Thermal device, high and low thresholds. 10 element bar graph indication.
Supply Voltage
18 to 30 VDC (24 VDC Nominal)
Relay Contact Ratings
1 A at 30 VDC
Maximum Supply Current
350 mA at 24 VDC with no aspirating pipe. See table below for typical
Currents/Fan Speeds.
Maximum Pipe Length
100 m + 100 m in Tee Configuration
Environmental Protection
IP65 with exhaust fitted (IP23 without)
Operating Temperature
-10 to 50ºC
Operating Humidity
10 to 95% RH (non-condensing)
Approvals
EN54-20 by VdS (G206066)
CE Certification
EN61000-6-3:2001(+A11:2004) (EMC)
EN60950-1:2006 (Safety)
CPD (89/106/EEC)
Table 11-2: Typical Current Consumption vs Fan Speed
Bargraph Value
0 1 2 3 4 5 6 7 8 9
Fan Speed
1 2 3 4 5 6 7 8 9 10
Current (mA)
110 120 130 150 170 190 220 235 265 300
Note:
Typical current consumption figures for different fan speeds. Results are based upon an ILS-1
installation with 10 m of standard, 25 mm aspirating pipe per channel. The unit was powered
from a 24 VDC power supply.