Replacing the chassis/Air Inlet Pipe Manifold
1.
Isolate unit by pressing the Isolate button on the zone configured display or by selecting
Isolate Zone
from the
Zone
menu in VSC or VSM4. This isolates the outputs from the unit
to a Fire Alarm Control Panel.
2.
Save node configuration by using VSC or VSM4, highlight the detector in the Device Tree
Window and select
Save Node Configuration
from the
Device
menu.
3.
Remove power by disconnecting the power cables.
4.
Remove the front panel by first opening the cover plate and screw covers, then unscrew the
front cover.
Figure 22 - Removing front cover
5.
Disconnect data cables connecting the chassis assembly to the termination card, front
panel modules (if fitted) and manifold.
Figure 23 - Remove data cables
6.
Unscrew the three manifold retaining screws
7.
Remove chassis, holding the chassis by the aspirator assembly. Release the two lower
locking tabs by lifting the chassis upward and pulling outward. Use a screwdriver to assist
with tab release.
A
B
Legend
A
Cover plate screws
B
Screw covers
Legend
C
Termination cable
D
Head processor card
E
Flow sensor cable
F
Scanner cable
C
D
E
F
Summary of Contents for VESDA VLP
Page 1: ...Xtralis VESDA VLP Product Guide August 2008 Document Number 10278_07 Part Number 19145 ...
Page 2: ......
Page 8: ...Xtralis VESDA VLP Product Guide Xtralis VESDA 2 www xtralis com ...
Page 19: ...Xtralis VESDA Xtralis VESDA VLP Product Guide www xtralis com 13 Figure 8 VLP dimensions ...
Page 46: ...Xtralis VESDA VLP Product Guide Xtralis VESDA 40 www xtralis com ...