Figure 24 - Remove the chassis
Caution:
Care must be taken not to damage the cable running to the manifold.
Note:
The chassis consists of the Detection Chamber, head processor card and flow
sensors. These are factory calibrated as a matched set and must not be separated.
Separating the set and replacing it with components from another VLP will cause
the detector to malfunction. This will require the chassis to be returned to the
factory.
8.
Disconnect the flow sensor lead.
9.
Unscrew manifold retaining screws.
Figure 25 - Removing pipe inlet manifold
10. Remove the manifold by sliding it downward, away from the pipe network.
11.
Attach the replacement manifold and chassis by reversing the procedure above.
12. Configure the node using VSC or VSM4 by highlighting the detector in the Device Tree
window and highlighting ‘Restore Node Configuration’ from the device menu, or reprogram
the detector using the LCD Programmer.
Note:
Data cables must be plugged and unplugged only after power has been removed.
Ensure all connectors are seated correctly before applying power to unit. Failure to
observe this requirement may cause data corruption that requires factory re-
calibration.
Summary of Contents for VESDA VLP
Page 1: ...Xtralis VESDA VLP Product Guide August 2008 Document Number 10278_07 Part Number 19145 ...
Page 2: ......
Page 8: ...Xtralis VESDA VLP Product Guide Xtralis VESDA 2 www xtralis com ...
Page 19: ...Xtralis VESDA Xtralis VESDA VLP Product Guide www xtralis com 13 Figure 8 VLP dimensions ...
Page 46: ...Xtralis VESDA VLP Product Guide Xtralis VESDA 40 www xtralis com ...