6615 W. Layton Ave. Milwaukee, WI 53220
Phone: (414) 282-4840 FAX: (414) 282-5670
E-Mail: [email protected]
Products Inc.
DORLEN
DORLEN
SYSTEMS INSTALLIED IN OVER 25,000 SITES!
Mfgr. of:
R
Oil Alert
Oil Alert
R
CEILING
GUARD
R
www.wateralert.com
www.oil-alert.com
LIQUID LEAK DETECTION SYSTEMS SINCE 1975
If you have installation questions,
call
toll free
1-800-533-6392
Instructions for
Model
SS
Water
Alert
®
(Model
XSS
when using Sensor Cable)
PRINCIPLE OF OPERATION
Refer to Figure 1. The SS is activated by liquid bridging the adjustable sensors (A & A). The unit can detect
water film from zero height, (sensors turned out to make contact with the floor), to 1/8" height, (sensors turned
all the way in). The units are factory adjusted to activate with 1/32" water film height which is satisfactory for
most applications. The pads B1, B2, B3 provide a gap between the case and the surface to admit water under
the unit for detection. CAUTION: If the pads are removed, the unit may form a seal with the surface and prohibit
the sensors from detecting water. If desired, the self-adhesive pad feature may be used by peeling off the thin
protective layer from each pad. The unit will remain in place when located on the mounting surface. Replace
-
ment pads are available from Dorlen at no charge.
NOTE:
Although the two sensors (A & A) may be adjusted to make contact with the surface, it is recommended
that a small gap be set between the sensors and the surface so undesired activation, caused by damp
-
ness or dirt film, does not occur.
1-19
M-9857
CAUTION
Not For Explosive Environments!
Page 1 of 2
Figure 1
WHEN WATER FILM FORMS
A BRIDGE BETWEEN SEN
-
SORS (A&A), WATER ALERT
IS ACTIVATED.
A
A
A
A
FLOOR
B2
B1
FLOOR
Powering options -
- 9v Alkaline Battery (Qty.1)
- PSW-3 Power Supply (Catalog Pg. 25)
- Voltage Module (Catalog Pg. 26)
Model SS Bottom View
5 YEAR
LIMITED
WARRANT
Y
See catalog or pr
ice
list for details