VESDA VFT-15 Product Guide
VESDA by Xtralis
44
www.xtralis.com
7.5
Area Covered
Area
Up to 1,500 m² (16,150 ft²)
7.6
Cabling
Access
7 x 25mm (1”) cable entries
Termination
Screw Terminal blocks 0.2–2.5 mm²
(30-12 AWG)
7.7
Interfaces
Power
Power In
Relays
4 Alarm Relays, 1 Fault Relay
Rated 2 A @ 30 VDC NO/NC Contacts
7.8
Alarm
Range
0.001 to 20 % obs/m
(0.0003 to 6.10 % obs/ft)
Levels
Trace, Alert, Action, Fire1, Fire2
Individually programmable for each level
7.9
Communication
Protocols
Modbus over RS232, RS485 and TCP/IP
7.10 Event Log
Storage
Up to 20,000 events stored