5. Display LEDs
LED
Description
Power
Indicates that the power supply is ON.
If the system processor is faulty, the General Fault, Power and Comms LEDs will be
activated simultaneously.
General Fault
The detector has one or more faults, which will also be shown by other specific fault
indicators. The Fault relay contacts always follow the state of this indicator.
Isolated will also show as General Fault.
If the system processor is faulty, the General Fault, Power and Comms LEDs will be
activated simultaneously.
Processor
Reset
This indicator activates briefly during the powerup initialization sequence.
Mains Fault
This indicator may activate due to an incorrect device configuration.
To prevent this from occurring, ensure that Pin 2 and Pin 5 on CN2 are linked.
Refer to page 13 for further information.
Flow Fault
The flow rate for any sector is outside the bounds set by the High and Low flow
limits.
Battery Fault
This indicator may activate due to an incorrect device configuration.
To prevent this from occurring, ensure that the STANDBY parameter in the
Configuration menu is set to 0. For more information, refer to Table 5-4.
Aspiration
Fault
The rotary valve has a fault.
Detector Fault
The laser smoke detector has developed a fault.
Isolated
This has been put into Isolated mode when the unit functions normally, but alarm
reporting via the relays is disabled.
Note:
General Fault will also be shown.
Comms Fault
An element of the internal RS485 communication link or remote display is faulty.
If the system processor is faulty, the General Fault, Power and Comms LEDs will be
activated simultaneously.
Hold
Flashes when a manual scan is being performed.
Unlock
The Panel is unlocked - meaning that an access code has been entered. It will
clear when normal operation is resumed.
Table 2-2: LED Descriptions
6. Alert, Action, Fire1, and Fire2 Indicators
These operate in tandem with corresponding relays on the I/O board to indicate progressive levels of smoke
and are programmable for obscuration level.
7. Logarithmic smoke density bar graph
Displays 0 to 20 % obs/m (0 - 6.09 %obs/ft) with a resolution of 0.001 % obs/m (0.0003% obs/ft) at the lower
end.