VESDA by Xtralis
VESDA VFT-15 Product Guide
www.xtralis.com
35
Parameter
Description
LASERIN
Current smoke value for the laser detector output
LASERHI
Additional smoke detector data (Factory Use)
LASERM
Additional smoke detector data (Factory Use)
LASERLO
Additional smoke detector data (Factory Use)
REL IN
Current Pressure Sensor reading
ABS IN
REL IN value at last flow normalization
PRSCOMP
Pressure sensor temperature compensation value
(Factory Use)
S1 COIL
Suppression Control Module S1 COIL value
S1 TEST
Suppression Control Module S1 TEST value
A1 COIL
Suppression Control Module A1 COIL value
A1 TEST
Suppression Control Module A1 TEST value
P1 NORM
Suppression Control Module P1 NORM value
P1 TEST
Suppression Control Module P1 TEST value
C1 NORM
Suppression Control Module C1 NORM value
C1 TEST
Suppression Control Module C1 TEST value
S2 COIL
Suppression Control Module S2 COIL value
S2 TEST
Suppression Control Module S2 TEST value
A2 COIL
Suppression Control Module A2 COIL value
A2 TEST
Suppression Control Module A2 TEST value
P2 NORM
Suppression Control Module P2 NORM value
P2 TEST
Suppression Control Module P2 TEST value
C2 NORM
Suppression Control Module C2 NORM value
C2 TEST
Suppression Control Module C2 TEST value
MOD1 IN
Identification number of Module 1
MOD2 IN
Identification number of Module 2
MOD3 IN
Identification number of Module 3
MOD4 IN
Identification number of Module 4
MOD5 IN
Identification number of Module 5
Table 5-8: Maintenance Parameters
5.3.12 TEST OUTPUTS: Testing Mode
Minimum Access Code Required:
Level 2
This menu item enables the user to manually increase or decrease smoke and flow levels for the detector in
order to simulate real fire and flow events. This enables the user to test the responses of the detector to fire
and flow events without the need to conduct smoke tests or blocking/unblocking the sampling network. Note
that all alarms and relays will operate as if the system is reacting to a real event.