VESDA by Xtralis
VESDA VFT-15 Product Guide
www.xtralis.com
33
5.3.8
SETUP: Setup Menu
Minimum Access Code Required:
Level 2
Once the Setup Mode is accessed, follow this procedure to change a parameter:
1. Press Parameter
UP
&
DOWN
buttons to reach required
SETUP
item.
2. Press
ENTER
.
3. Press Value
UP
&
DOWN
buttons to update the item.
4. Press
ENTER
to update and move to next parameter. If the value is left unchanged,
ENTER
will have
no effect.
Press
MENU
to get back to the Main Menu. Press
MENU
again to get back to Normal display.
The Setup menu has the following items.
Parameter
Value
Defaults
Description
HI RESLTN 0 or 1
0
Enables the Status Display to show standard resolution (0) or
higher Resolution (1) for obscuration (switches between a
resolution of 0.01 to 0.001).
Note:
It is highly recommended to leave this value at 0.
Changing the value from 0 will cause some configuration
values to change. Connection to the Xtralis VSC
software will automatically change this value back to 0.
OBSC/FT
0 or 1
0
Set to 1 to display smoke value in % obs/ft. Normally % obs/m.
Note:
Smoke Alarm Thresholds will revert to default values
when changing between % obs/ft and % obs/m and vice
versa.
REMPANEL 0 or 1
0
Enables remote panel operation. A communications fault will be
displayed if this is enabled without a remote display connected.
REMPOD
0, 1 or 2
0
Set to 1 if a Remote Sensing Unit is connected.
Note:
This option is not available for standard VFT detectors.
DETFLOW
0 or 1
1
In addition to individual sector flow monitoring, detector flow
monitoring is also incorporated.
Set to 1 to enable.
CCODE
Country Code
Refer to Table 5-7.
RES-ISOL
0 or 1
1
Set to 0 to reset system with 24 V on reset line.
Set to 1 to isolate system when 24 V is applied for 8 seconds or
more.
Note:
Once 24 V is applied, the system will initially reset. If 24
V is still present after 8 seconds, the system will be
isolated until 24 V is removed (after which it will resume
normal operation). If the 24 V is removed before 8
seconds, the system will only reset and will not be
isolated.
MOD1 to 5
List of available I/O
modules
All I/O modules fitted at build will have this information entered. If
additional I/O modules are installed, their type must be entered
here.
Table 5-6: Setup Menu Parameters and Values