VESDA Commissioning Guide
VESDA by Xtralis
22
www.xtralis.com
1. Ensure that the local fire panel is isolated from the external fire reporting equipment and that any
automatic extinguishing or suppressant systems are also isolated.
2. With the power turned off, connect each end of a 1 meter (3 ft.) length of the specified wire to the VTT-
10000.
3. Ensure that the wire is laid on an insulating board to avoid damage to the floor.
4. Check that there are no kinks or crossovers in the wire.
5. Connect power to the VTT-10000 and turn the power on for 180 seconds.
At this point, there is 6 VAC applied across the test wire, the switch will illuminate and the green indicator on
the timer will begin to flash. The test wire will become hot and a small quantity of smoke will be generated.
6. Turn the unit off after the timed burn period is complete.
Figure 5-3: Wire Burn Test Kit VTT-10000
7. Record the response time of the detector.
8. For multiple tests, allow 5 minutes (300 seconds) between tests so all smoke can dissipate.
Caution:
The test wires will become very hot. Do not touch.
Enter the following results on the commissioning form:
l
Transport Time - Introduce smoke at the furthest sampling hole from the detector. The time taken (in
seconds) for the smoke to travel to the detector is the transport time. If there is a wide variation between
the ASPIRE2 predictions and the test results, the pipe network should be checked for leaks, blockage
and to see that the installed pipe network matches the model used in ASPIRE2.
l
Initial Response - This is the total of the time taken for the smoke to travel from the source to the
sampling point and the detector first registering the presence of smoke (excluding any alarm delay times
that may have been set).
l
Alert Response - The time taken for initial response and the detector to generate an Alert Alarm
l
Action/Pre-Alarm - The time taken for alert and the detector to generate an Action/Pre-Alarm status
(excluding any delay times)
l
Fire 1/Fire Response - The time taken for alert and the detector to generate an Fire 1/Fire Response
status (excluding any delay times)
l
Fire 2 Response - The time taken for alert and the detector to generate an Fire 2/Fire Response status
(excluding any delay times)
l
Peak Smoke Response - This is the time taken for the detector to record the peak level of smoke
(excluding any delay times). The numerical display of the display module or the LCD Programmer will
display the smoke levels. This information can also be extracted from the event log.
Acceptable response times are determined by site requirements, subject to local codes and standards. In the
event the test response times do not meet the acceptable standard the commissioning form should be signed
as NOT ACCEPTABLE and recommendations for further work should be recorded on the commissioning
form.
Summary of Contents for VESDA E-Series
Page 1: ...VESDA Student Workbook Rev 8a 15SEP21...
Page 4: ...iv...
Page 14: ...VESDA Course Overview 1 10 VESDA Student Workbook Create Xtralis Account...
Page 20: ...VESDA Course Overview 1 16 VESDA Student Workbook...
Page 23: ...VESDA Products VESDA Student Workbook 2 3 ASD iVESDA ASD...
Page 24: ...VESDA Products 2 4 VESDA Student Workbook VESDA model comparison chart...
Page 32: ...VESDA Products 2 12 VESDA Student Workbook Industrial facilities Industrial facilities...
Page 33: ...VESDA Products VESDA Student Workbook 2 13 Solutions for all environments Detectors...
Page 56: ...Installation 3 4 VESDA Student Workbook IDP Installation Practices...
Page 68: ...Installation 3 16 VESDA Student Workbook...
Page 74: ...VESDAnet Connection 4 6 VESDA Student Workbook...
Page 218: ...VSC Software Installation A 4 VESDA Student Workbook...
Page 224: ...ASPIRE Software Installation B 6 VESDA Student Workbook...
Page 238: ...14...
Page 239: ...VESDA Pipe Network Design Guide February 2019 Document 10193_09 Part Number 30009...
Page 240: ......
Page 293: ...VESDA Pipe Network Installation Guide March 2019 Document 10255_08 Part Number 30008...
Page 294: ......
Page 333: ......
Page 334: ...VESDA Commissioning Guide December 2012 Document 10195_06 Part Number 30005...
Page 335: ......