VESDA Pipe Network Installation Guide
VESDA by Xtralis
22
www.xtralis.com
Generally, a VESDA VLP or VESDA VLS detector should not monitor more than four AHUs, a VESDA VLC
should not monitor more than two, and a VESDA VLF should not monitor more than one AHU.
Legend
A
Sampling Pipe
B
Return grille
C
End cap without a hole
D
Sampling hole
Figure 5-10: Sampling over a return air grille
5. Drill sampling holes as specified in the design documents.
6. The pipework must always have an end cap without a hole in it.
5.2.2
Supply Air Sampling
Refer to Return Air Grilles (Section 5.2.1), or use a Duct design (Section 5.2.3).
Summary of Contents for VESDA E-Series
Page 1: ...VESDA Student Workbook Rev 8a 15SEP21...
Page 4: ...iv...
Page 14: ...VESDA Course Overview 1 10 VESDA Student Workbook Create Xtralis Account...
Page 20: ...VESDA Course Overview 1 16 VESDA Student Workbook...
Page 23: ...VESDA Products VESDA Student Workbook 2 3 ASD iVESDA ASD...
Page 24: ...VESDA Products 2 4 VESDA Student Workbook VESDA model comparison chart...
Page 32: ...VESDA Products 2 12 VESDA Student Workbook Industrial facilities Industrial facilities...
Page 33: ...VESDA Products VESDA Student Workbook 2 13 Solutions for all environments Detectors...
Page 56: ...Installation 3 4 VESDA Student Workbook IDP Installation Practices...
Page 68: ...Installation 3 16 VESDA Student Workbook...
Page 74: ...VESDAnet Connection 4 6 VESDA Student Workbook...
Page 218: ...VSC Software Installation A 4 VESDA Student Workbook...
Page 224: ...ASPIRE Software Installation B 6 VESDA Student Workbook...
Page 238: ...14...
Page 239: ...VESDA Pipe Network Design Guide February 2019 Document 10193_09 Part Number 30009...
Page 240: ......
Page 293: ...VESDA Pipe Network Installation Guide March 2019 Document 10255_08 Part Number 30008...
Page 294: ......
Page 333: ......
Page 334: ...VESDA Commissioning Guide December 2012 Document 10195_06 Part Number 30005...
Page 335: ......