System Configuration and Setting Thresholds
Different detectors are configured in different ways.
For VESDA VLP, VESDA VLS and VESDA VLC please use the instructions for Generic Configuration in
Section 4.1. Once you have completed these steps you can configure the settings specific to each detector.
The VESDA VLF was designed with ease of configuration in mind. No specialized hardware or software tools
are required to configure this detector as it will autolearn about its environment once it is installed.
The VESDA VFT-15 is covered in Section 4.3 on page 15.
4.1
Generic Configuration (VLC, VLS, VLP)
When the system is powered up for the first time, any LCD Programmer or PC Software connected to
VESDAnet will register all the detectors and display modules as unconfigured. All other VESDA laser range of
products will appear under ancillary devices. Each laser device has a built in unique number and this number
is displayed next to the device.
For detailed explanation of the LCD Programmer Screens, and the Xtralis VSC Forms and Tabs mentioned in
the table below, please refer to the LCD Programmer Guide and the Xtralis VSC Online Help respectively.
Setting Date and Time
l
For LCD Programmer: See LCD screen 144
l
For Xtralis VSC: See VESDAnet Form Clock Set Tab
Setting Units
l
For LCD Programmer: See LCD screen 157 and select SI (for International System of Units) or US (for
US Imperial measurements)
l
For Xtralis VSC: See VESDAnet Form Units Tab
Configuring a Detector to a VESDA Zone
For LCD Programmer:
l
See LCD screen 4 to select a detector
l
See LCD screen 21, 41 & 91 to assign a VESDA zone number to the detector
l
See LCD screen 22, 4, 2, 92 to assign an address name and/or location
More experienced technicians prefer to use the Drag and drop function.
For Xtralis VSC:
1. Press insert, then drag and drop the devices into their respective addresses
2. Select Address name/location tab and enter a suitable name/location for the detector
Assigning a display module to a detector
For LCD Programmer: See LCD screen 110
1. Select the relevant display module.
2. Give it the same address number as the assigned detector
3. Enter the address name/location of the display
For Xtralis VSC: Select Device Tree/Menu
1. Select the display on the device tree
2. Select address Configuration Tab to enter the address number
3. Select address name/location tab and enter respective address name/location
Reference detector configuration
For LCD Programmer: See LCD screen 28, 67, 97
1. Give a reference address number or enter 255 if there is no reference detector.
2. Set the dilution factor
3. Set the delay time
Summary of Contents for VESDA E-Series
Page 1: ...VESDA Student Workbook Rev 8a 15SEP21...
Page 4: ...iv...
Page 14: ...VESDA Course Overview 1 10 VESDA Student Workbook Create Xtralis Account...
Page 20: ...VESDA Course Overview 1 16 VESDA Student Workbook...
Page 23: ...VESDA Products VESDA Student Workbook 2 3 ASD iVESDA ASD...
Page 24: ...VESDA Products 2 4 VESDA Student Workbook VESDA model comparison chart...
Page 32: ...VESDA Products 2 12 VESDA Student Workbook Industrial facilities Industrial facilities...
Page 33: ...VESDA Products VESDA Student Workbook 2 13 Solutions for all environments Detectors...
Page 56: ...Installation 3 4 VESDA Student Workbook IDP Installation Practices...
Page 68: ...Installation 3 16 VESDA Student Workbook...
Page 74: ...VESDAnet Connection 4 6 VESDA Student Workbook...
Page 218: ...VSC Software Installation A 4 VESDA Student Workbook...
Page 224: ...ASPIRE Software Installation B 6 VESDA Student Workbook...
Page 238: ...14...
Page 239: ...VESDA Pipe Network Design Guide February 2019 Document 10193_09 Part Number 30009...
Page 240: ......
Page 293: ...VESDA Pipe Network Installation Guide March 2019 Document 10255_08 Part Number 30008...
Page 294: ......
Page 333: ......
Page 334: ...VESDA Commissioning Guide December 2012 Document 10195_06 Part Number 30005...
Page 335: ......