HOOD THEORY OF OPERATION (STD W/FS)
Switch Relocation Cord (SRC) connects into these. This deactivates the main oven switch located
on the oven and relocates the operation of it to the HUI. This capacitive touch (NO) switch is lo
cated on the front of the hood and controls the lights.
TS 1
&
2-
These are terminal strips, that serve as a connection point for wires.
VFD
- The Variable Frequency Drive (VFD) converts the AC supply voltage to DC and then con
verts the DC to a suitable three-phase frequency source for Ml. Incoming power connects to ter
minals LI & L2. Ml connects to terminals Tl, T2, & T3 through TSI. The HMC sends the com
mand to the ModBus to set the frequency for the combination of ovens selected. The VFD can re
ceive a signal from the fire suppression system to command the drive to run at 60 Hz. A complete
manual can be found at
www.x
lt
o
v
ens.com
.
Exha ust Fan Speed
Exha ust Fan On
Ala rm Mute
Error Informa tion