FusionServer CH242 V5 Compute Node
Technical White Paper
6 Product Specifications
2022-08-12
38
Category
Specifications
⚫
Storage temperature (within six months): –15°C to +45°C
(5°F to 113°F)
⚫
Storage temperature (within one year): –10°C to +35°C
(14°F to 95°F)
⚫
Maximum rate of temperature change: 20°C (36°F) per
hour, 5°C (9°F) per 15 minutes
NOTE
If Intel
®
Xeon
®
Scalable processors (Platinum 8180, 8180M, 8168 or
Gold 6144, 6146, 6154) are used, the maximum operating temperature
supported is 35°C (95°F).
Relative humidity (RH,
non-condensing)
⚫
Operating humidity: 5% to 85%
⚫
Storage humidity (within three months): 8% to 85%
⚫
Storage humidity (within six months): 8% to 80%
⚫
Storage humidity (within one year): 20% to 75%
⚫
Maximum change rate: 20%/h
Operating altitude
≤3050m
⚫
When the server configuration complies with ASHRAE
Classes A1 and A2 and the altitude is above 900 m
(2952.76 ft), the highest operating temperature decreases by
1°C (1.8°F) for every increase of 300 m (984.25 ft).
⚫
When the configuration complies with ASHRAE Class A3
standards and the altitude is above 900 m (2952.76 ft.), the
highest operating temperature decreases by 1°C (1.8°F) for
every increase of 175 m (574.14 ft.).
⚫
HDDs cannot be used at an altitude of over 3050 m
(10006.44 ft).
Corrosive gaseous
contaminant
Maximum corrosion product thickness growth rate:
⚫
Copper corrosion rate test: 300 Å/month (meeting level G1
requirements of the ANSI/ISA-71.04-2013 standard on
gaseous corrosion)
⚫
Silver corrosion rate test: 200 Å/month
Particle contaminant
⚫
The equipment room environment meets the requirements
of ISO 14664-1 Class 8.
⚫
There is no explosive, conductive, magnetic, or corrosive
dust in the equipment room.
NOTE
It is recommended that the particulate pollution in the equipment room
be monitored by a professional agency.
SSDs and HDDs (including NL-SAS, SAS, and SATA) cannot be preserved for a long time in the
power-off state. Data may be lost or faults may occur if the preservation duration exceeds the specified
maximum duration. When drives are preserved under the storage temperature and humidity specified in
the preceding table, the following preservation time is recommended: