Category
Specifications
Corrosive gaseous
contaminant
Maximum corrosion product thickness growth rate:
● Copper corrosion rate test: 300 Å/month (meeting
level G1 requirements of the ANSI/ISA-71.04-2013
standard on gaseous corrosion)
● Silver corrosion rate test: 200 Å/month
Particle contaminant
● The equipment room environment meets the
requirements of ISO 14664-1 Class 8.
● There is no explosive, conductive, magnetic, or
corrosive dust in the equipment room.
NOTE
It is recommended that the particulate pollutants in the
equipment room be monitored by a professional organization.
Acoustic noise
The declared A-weighted sound power levels (LWAd)
and declared average bystander position A-weighted
sound pressure levels (LpAm) listed are measured at
23°C (73.4°F) in accordance with ISO 7779 (ECMA 74)
and declared in accordance with ISO 9296 (ECMA 109).
● Idle:
– LWAd: 6.2 Bels
– LpAm: 45.3 dBA
● Operating:
– LWAd: 6.97 Bels
– LpAm: 52.6 dBA
NOTE
Actual sound levels generated during server operation vary
depending on server configuration, load, and ambient
temperature.
NO TE
SSDs and HDDs (including NL-SAS, SAS, and SATA) cannot be preserved for a long time in
the power-off state. Data may be lost or faults may occur if the preservation duration exceeds
the specified maximum duration. When drives are preserved under the storage temperature
and humidity specified in the preceding table, the following preservation time is recommended:
● Maximum preservation duration of SSDs:
●
12 months in power-off state without data stored
●
3 months in power-off state with data stored
● Maximum preservation duration of HDDs:
●
6 months in unpacked/packed and powered-off state
● The maximum preservation duration is determined according to the preservation
specifications provided by drive vendors. For details, see the manuals provided by drive
vendors.