6.2 Environmental Specifications
Table 6-2
Environmental specifications
Category
Specifications
Temperature
● Operating temperature: 5°C to 45°C (41°F to 113°F)
(ASHRAE Classes A1 to A4 compliant)
● Storage temperature (within three months): –30°C to
+60°C (–22°F to 140°F)
● Storage temperature (within six months): –15°C to
+45°C (5°F to 113°F)
● Storage temperature (within one year): –10°C to
+35°C (14°F to 95°F)
● Maximum rate of temperature change: 20°C (36°F)
per hour, 5°C (9°F) per 15 minutes
NOTE
The highest operating temperature varies depending on the
server configuration. For details, see
.
Relative humidity (RH,
non-condensing)
● Operating humidity: 8% to 90%
● Storage humidity (within three months): 8% to 85%
● Storage humidity (within six months): 8% to 80%
● Storage humidity (within one year): 20% to 75%
● Maximum humidity change rate: 20%/h
Air volume
≥ 96 cubic feet per minute (CFM)
Operating altitude
≤ 3050 m (10006.56 ft)
● When the server configuration complies with ASHRAE
Classes A1 and A2 and the altitude is above 900 m
(2952.76 ft), the highest operating temperature
decreases by 1°C (1.8°F) for every increase of 300 m
(984.24 ft).
● When the server configuration complies with ASHRAE
Class A3 and the altitude is above 900 m (2952.76 ft),
the highest operating temperature decreases by 1°C
(1.8°F) for every increase of 175 m (574.14 ft).
● When the server configuration complies with ASHRAE
Class A4 and the altitude is above 900 m (2952.76 ft),
the highest operating temperature decreases by 1°C
(1.8°F) for every increase of 125 m (410.1 ft).
● HDDs cannot be used at an altitude of over 3050 m
(10006.44 ft).
FusionServer 1288H V6 Server
Technical White Paper
6 Product Specifications
Issue 10 (2023-04-30)
Copyright © xFusion Digital Technologies Co., Ltd.
65