Monitoring Operation
2–2
975-0240-01-01
Monitoring Operation with the Inverter Information Panel
The Inverter Information Panel displays basic information that enables you to
monitor a single XW Inverter/Charger. The Inverter Information Panel also allows
you to turn the XW Inverter/Charger on and off and start battery equalization.
LEDs on the Information Panel indicate AC input status, inverter status, battery
condition, and charging and equalization status. The LEDs and three-character
display screen also alert you to XW Inverter/Charger warning and fault
conditions.
Monitoring AC Input Status
Grid (AC1)
The green Grid (AC1) LED indicates the presence and status of AC
source connected to the AC1 input. In most installations, AC1 input is from the
utility grid. However, any AC source can be connected to the AC1 input.
Gen (AC2)
The green Gen (AC2) LED indicates the presence and status of a
generator or other auxiliary AC source on the AC2 input.
Figure 2-1
Inverter Information Panel
Grid (AC1)
Gen (AC2)
Fault /
Warning
Equalize
Battery
Charging
Inverting
flashing = sell
kW
A
8
.
88
Symbol
LED On
LED Flashing
LED Off
AC input is present and qualified.
The XW Inverter/Charger is ready to
charge batteries, sell power to the
grid, or pass AC through to the loads.
AC input is
present, within
nominal range
and is being
qualified.
The XW
Inverter/Charger
is not connected
to the grid. AC
input is not
present, or AC
input is present
but not within
nominal range.