Features and Specifications
Additional Electrical Specifications
26
Operating Manual for XHR Series Power Supply
Additional Electrical Specifications
Input Conditions
Voltage Mode Transient Response
(Time for the output voltage to
recover within 0.5% of its
previous level after a step change
in load current of up to 50% of the
rated output.)
1 ms
Time delay from power on until
output stable
4 s maximum
Rated AC Input Voltage
100/120/200/220/230/240 Vac (nominal)
Maximum AC Input Rating
1300 VA
Operational AC Input Voltage
Range
85-250 Vac; power factor corrected.
Derate maximum output power to 900 W for
AC input less than 95 V.
Maximum Input Current
13 A maximum at 100 Vac,
11 A maximum at 120 Vac,
6 A maximum at 220 Vac.
Input Frequency Range
47
–
63 Hz
Power Factor
0.99 minimum for full load and 120 Vac
input
TM-XROP-01XN.book Page 26 Monday, March 22, 2004 4:10 PM