Connecting the DC Cables
975-0263-01-01
3–19
Ensure you have maintained correct polarity and that there are no loose
strands of wire.
13. Secure the strain-relief clamp.
14. Attach the wiring compartment cover.
15. Connect the outgoing AC wires to the AC load panel.
Connecting the DC Cables
Consult Figure 3-1, “DC Input Configuration for Normal Loads” on page 3–
2, or, Figure 3-2, “DC Input Configuration for Heavy Loads” on page 3–3,
for additional details that are specific to your installation.
To connect the DC cables:
1. Make sure the inverter is off and no AC is connected to the unit.
2. Remove the nuts and washers from the XM Series Inverter positive and
negative DC cabling terminals.
3. Strip 1/2 inch (13 mm) to 3/4 inch (19 mm) insulation from one end of
each cable. The amount stripped off will depend on the terminals
chosen.
4. Attach the connectors that will join the cables to the battery, disconnect/
battery selector switch, and fuse block. The connectors you use must
create a permanent, low-resistance connection.
If you are using crimp connectors, use the tool recommended by the
terminal manufacturer. Make sure no stray wires protrude from the
terminal.
(You may find it more convenient to have the crimp connectors attached
by the company that sells you the cable and/or connectors.)
5. For each cable end that will be connected to the inverter, strip 1/2 inch
(13 mm) to 3/4 inch (19 mm) of insulation from the cable. The amount
stripped off will depend on the terminals chosen.
6. Thread a supplied DC terminal cover over the positive and negative
cables. The red cover goes on the positive cable; the black cover on the
negative cable.
7. Attach the connector that will join the cable to the DC cabling terminal.
8. Install a fuse and fuse holder in the cable that will be used for the
positive side of the DC circuit.
The fuse must be:
Summary of Contents for Xantrex PRO XM 1000