AC Wiring
975-0263-01-01
3–15
When making the AC input and AC output connections, observe the
correct color code for the appropriate AC wire, as described in Table 3-4.
Connecting AC Input
1. Install the required circuit breaker in the AC output panel supplying
the unit.
2. Ensure AC power is disconnected from the wire you intend to
connect to the XM Series Inverter.
3. Remove the screws securing the GFCI and pull out the GFCI.
4. Remove the GFCI.
5. Remove the right-hand side AC wiring knockout from the front of the
unit (see Figure 3-5).
6. Install a supplied strain-relief clamp in the AC knockout.
7. Locate the terminal block.
The two input terminals are labelled as follows:
•
N (neutral)
•
L (line)
A separate screw is provided to connect the AC input ground (see
Figure 3-5).
Table 3-4
Color codes for typical AC wiring
Color
AC Wire
Black
Line
White
Neutral
Green or bare copper
Ground
WARNING: Shock, fire, and energy hazards
Make sure wiring is disconnected from all electrical sources before handling. All
wiring must be done in accordance with local and national electrical wiring
codes. Do not connect the output leads of the inverter to any incoming AC
source.