Multi-wire Branch Circuit Wiring
F–4
976-0043-01-02
Identifying Multi-wire Branch Circuits
Identifying
characteristic
Multi-wire branch circuits can be identified by removing the cover on the
load center and inspecting the wiring. Conventional 120 Vac circuits are
identified by a 2-wire-plus-ground (black, white, and copper) “romex” for
each circuit. Multi-wire branch circuits use a 3-wire-plus-ground
arrangement (black, red, white and copper) for each circuit run.
If this arrangement exists in the panel and it is being powered by a stand-
alone 120 Vac inverter, a potential fire hazard exists! For safety, these
circuits must be rewired to meet code.
WARNING: Shock Hazard
The next step involves opening the load center, exposing live circuits. This
procedure should only be performed by qualified persons or electricians.
Figure F-4
Multi-wire Branch Circuit Wiring
Ground Bare
Copper
Single Neutral
White
Red From L2
Breaker
Red From L1
Breaker
To Branch Circuits
Summary of Contents for SW Plus 2524
Page 2: ......
Page 3: ...Sine Wave Plus Inverter Charger Owner s Manual...
Page 82: ...2 48...
Page 105: ...DC Wiring 976 0043 01 02 3 23 Figure 3 13 DC Connections to a Single Inverter...
Page 107: ...DC Wiring 976 0043 01 02 3 25 Figure 3 14 DC Connections to Dual Inverters...
Page 126: ...3 44...
Page 132: ...4 6...
Page 141: ...Menu Map 976 0043 01 02 5 9 Figure 5 10 User Menu Map Part 2...
Page 143: ...Menu Map 976 0043 01 02 5 11 Figure 5 12 Basic Setup Menu Map Part 2...
Page 145: ...Menu Map 976 0043 01 02 5 13 Figure 5 14 Advanced Setup Menu Map Part 2...
Page 146: ...Navigation 5 14 976 0043 01 02 Figure 5 15 Complete User Menu Map...
Page 147: ...Menu Map 976 0043 01 02 5 15 Figure 5 16 Complete Basic Setup Menu Map...
Page 148: ...Navigation 5 16 976 0043 01 02 Figure 5 17 Complete Advanced Setup Menu Map...
Page 250: ...8 32...
Page 274: ...A 16...
Page 308: ...C 18...
Page 312: ...D 4...
Page 316: ...E 4...
Page 338: ...I 6...
Page 342: ...Index IX 4 976 0043 01 02...
Page 343: ......