Operation
8–28
976-0043-01-02
05H Gen Failed to Start
If “Yes” is displayed, the automatic generator-start system did not
successfully start the generator.
The system completes six start cycles and requires the generator to
operate for a minimum of five minutes before the starting attempts
counter is cleared.
To manually clear this error, press the green GEN buttons to directly
access the menu item 02A Generator and select OFF.
05I Gen Stopped Due to V/F
If “Yes” is displayed, the automatic generator-start system did not
successfully connect to the generator after it was running. If the generator
runs for 20 minutes without meeting the AC voltage and frequency
tolerance window, the automatic start-system stops the generator (after
the cooldown period) and indicates the error.
Whenever this error occurs, the inverter is prevented from starting the
generator until this error is cleared.
To clear this error, select OFF from menu item 02A Generator.
Determine and correct the reason the generator was out-of-tolerance, then
select AUTO from menu item 02A Generator if you want the generator
start system to be enabled.
06 Status Menu
The 06 Status Menu displays various conditions or special operating
modes of the inverter/charger in one convenient location. The information
in these displays is read-only and cannot be altered. Refer to this menu
whenever the yellow STATUS LED is illuminated.
A “No” displayed in this series of menu items indicate that no status
condition has occurred and provides no additional information. If the
Status light is on, scroll through the Menu Items under this Menu Heading
to look for a “Yes” to determine what’s happening.
05H Gen Failed to
Start
YES
05I Gen Stopped
Due to V/F YES
06 Status Menu
Summary of Contents for SW Plus 2524
Page 2: ......
Page 3: ...Sine Wave Plus Inverter Charger Owner s Manual...
Page 82: ...2 48...
Page 105: ...DC Wiring 976 0043 01 02 3 23 Figure 3 13 DC Connections to a Single Inverter...
Page 107: ...DC Wiring 976 0043 01 02 3 25 Figure 3 14 DC Connections to Dual Inverters...
Page 126: ...3 44...
Page 132: ...4 6...
Page 141: ...Menu Map 976 0043 01 02 5 9 Figure 5 10 User Menu Map Part 2...
Page 143: ...Menu Map 976 0043 01 02 5 11 Figure 5 12 Basic Setup Menu Map Part 2...
Page 145: ...Menu Map 976 0043 01 02 5 13 Figure 5 14 Advanced Setup Menu Map Part 2...
Page 146: ...Navigation 5 14 976 0043 01 02 Figure 5 15 Complete User Menu Map...
Page 147: ...Menu Map 976 0043 01 02 5 15 Figure 5 16 Complete Basic Setup Menu Map...
Page 148: ...Navigation 5 16 976 0043 01 02 Figure 5 17 Complete Advanced Setup Menu Map...
Page 250: ...8 32...
Page 274: ...A 16...
Page 308: ...C 18...
Page 312: ...D 4...
Page 316: ...E 4...
Page 338: ...I 6...
Page 342: ...Index IX 4 976 0043 01 02...
Page 343: ......