Basic Installation Procedures
34
Freedom XC 2000 (230VAC) Owner's Guide
AC Output Connections
Figure 11 Routing and connecting the wires
N
L
G
N
L
G
N
L
G
2
1
3
4
5
1
step 7a
2
step 7b
3
step 7c
4
15mm
5
to circuit breaker
NOTE
: AC Output hole - install a bushing (supplied) or a strain-relief
device.
To make a permanent connection to existing AC wiring:
1. Ensure AC and DC power sources are turned off, if not
already done from
AC Output Connections on page 34
.
2. Install the required circuit breaker in the inverter/charger
distribution panel receiving AC power from the
inverter/charger.
3. Remove the wiring compartment cover, if not already done
from
AC Output Connections on page 34
WARNING
ELECTRIC SHOCK HAZARD
Use a screwdriver to loosen the captive nut panel screw.
Failure to follow these instructions can result in death, serious
injury, or equipment damage
.
4. Strip a single AC output wire, as appropriate. Strip 10 mm off
the ends of each of the three the wires (tin the exposed
copper wire with lead-free solder using a soldering iron).
5. Remove the knockout and install 13mm (or 19mm) strain
relief clamp.
6. Route the wires through the strain relief clamp (not shown in
the figure
7. Connect each AC wire into its corresponding terminal on the
no-tool cage clamp terminal block.
a. Lift the terminal lever (as shown on the figure).
b. Insert the wire fully into the open slot.
c. Lower the terminal lever to secure the wire in the slot.
8. Make sure that each AC wire is matched and connected to
the Neutral (
N
), Earth (
G
), and Line (
L
) connections.
Summary of Contents for Freedom XC 2000
Page 1: ...Freedom XC 2000 230VAC Inverter Charger Owner s Guide Freedom XC 2000 230VAC 817 2080 12...
Page 20: ...This page is intentionally left blank 2...
Page 28: ...This page is intentionally left blank 2...
Page 32: ...This page is intentionally left blank 2...
Page 98: ...This page is intentionally left blank 2...