46
Freedom SW Owner’s Guide
Configuring the Freedom SW using the SCP
Inverter Settings Menu
The
Inverter Settings
menu contains settings that control when the
Freedom SW starts and stops producing AC output.
Figure 24
Inv
erter
Settings
Menu Screen
Table 8
Setting Defaults and Ranges
Model
Freedom SW 2012 / 3012
Freedom SW 2024 / 3024
Item
Default
Min
Max
Default
Min
Max
Low Batt Cut Out
10.5V
10.0V
12.0V
21.0V
20.0V
24.0V
LBCO Delay
10sec
0sec
600sec
10sec
0sec
600sec
Hi Batt Cut Out
16.5V
14.5V
17.0V
33.0V
29.0V
15.5V
Search Watts
50W
25W
250W
50W
25W
250W
Search Delay
2sec
1sec
25sec
2sec
1sec
25sec
FSW3012 00: Inv Settings
Low Batt Cut Out
LBCO Delay
Hi Batt Cut Out
Search Watts
Search Delay
[11.0]
[10sec]
[15.5V]
[50W]
[2sec]
Follow procedures on “To select and change a
configurable setting:” on page 33 to change the settings.
Table 9
Inverter Settings Description
Item
Description
Low Batt Cut Out
Low Battery Cut Out (LBCO) controls when the inverter stops
producing AC output due to a low battery voltage condition. The
inverter will stop producing AC output only after this level has been
reached for the period of time set by the
LBCO Delay
. This setting is
not temperature compensated.
LBCO Delay
LBCO Delay controls how long the inverter is allowed to operate at or
below the
Low Batt Cut Out
level before turning off due to a low
battery voltage condition. The inverter will stop producing AC output
only after the
Low Batt Cut Out
level has been reached for this
uninterrupted period of time.
Once the inverter has shut off, the battery voltage must rise 2 volts
above the
Low Batt Cut Out
setting (4 volts for 24-volt systems) for
inverter operation to resume.
Hi Batt Cut Out
Hi Batt Cut Out sets the maximum battery voltage at which the inverter
will operate. If the battery voltage exceeds this limit for more than one
minute, the Freedom SW displays a fault message and shuts down. The
inverter will not support AC loads when in this condition. If a qualified
AC source is present, the unit passes AC through to the loads. The
inverter automatically restarts when the voltage drops to 1.5 volts
(12 volt system) or 3 volts (24 volt system) below the
Hi Batt Cut
Out
setting. If battery voltage continues to rise after shutdown, an
external charger may still be charging the batteries. The Freedom SW
cannot control how external chargers operate.
Search Watts
Search Watts sets the Freedom SW’s search sensitivity when search
mode is enabled. When a load larger than this setting is present, the
inverter starts producing AC output. Enabling search mode from the
Setup
menu (see page 57) can minimize power draw from the battery
during periods of low demand from loads. Also see “Using Search
Mode” on page 34.
Freedom SW 3K2K InvChg Owners Guide.book Page 46 Wednesday, October 9, 2013 1:34 PM