975-0787-01-01
15
Basic Installation Procedures
This
section for use by
qualified per
sonnel
only.
AC Output Neutral Bonding
The neutral conductor of the Freedom X’s AC output circuit (that is,
AC Output Neutral) is automatically connected to the safety ground
during inverter operation. When AC utility power is present this
connection is not present, so that the utility neutral (that is, AC
Input Neutral) is only connected to utility ground at your source.
This conforms to the National Electrical Code (NEC), which
requires that separately derived AC sources (such as inverters and
generators) have their neutral conductors tied to ground in the same
way that the neutral conductor from the utility is tied to ground in
only one place. Check the regulations for your specific application
to ensure that the installation will comply with the necessary
requirements. In other words, the AC Input Neutral and Output
Neutral must be isolated from each other.
AC Grounding
As per UL458 SA29.5, for all permanently connected marine
inverters: The Freedom X should be connected to a grounded,
metal, permanent wiring system. Also, make sure that an AC
ground wire is connected to the AC ground terminal on the unit. Do
not just connect the line and neutral wires.
All connections to the unit should comply with all local codes and
ordinances.
DC Cabling
This includes all the cables and connectors between the batteries,
the DC disconnect and over-current protection device, and the
Freedom X. Most mobile installations require multi-strand insulated
cables for flexibility and durability in high vibration environments
and require disconnects and over-current devices. Electrical wiring
sizes in North America are indicated by AWG notation. In other
parts of the world, the metric system is used. Under the AWG
standard, a larger gauge number indicates a smaller wire diameter.
Wire size is usually marked on the larger sized cables. Table 2
specifies the minimum recommended DC cable size and maximum
fuse size for the Freedom X.
The DC cables must be copper and
must be rated 75 °C minimum.
The cables should be terminated
with lugs that fit the DC stud terminals snugly (
5
/
16
" hole size).
Table 2
Recommended Cable and Fuse Sizes
Inverter
Cable Length:
Battery to Inverter
(one way)
Minimum
Cable Size
Maximum
battery Fuse
Size
Freedom X 1000 120VAC
Less than 5 feet
(1.5 meters)
No. 2 AWG
150 A DC
Freedom X 2000 120VAC
Less than 5 feet
(1.5 meters)
No. 2/0 AWG
250 A DC
NOTE
: It is not recommended using a cable longer than 5 feet (1.5 meters) in each
direction. North American cable sizes above are based on the US National Electrical
Code Table 310.17 - 75 °C cables, assuming an ambient temperature of 30
°
C cables.
Freedom X Series INV Owners Guide.book Page 15 Tuesday, June 27, 2017 4:10 PM
Summary of Contents for 817-1000
Page 2: ...Freedom X Series INV Owners Guide book Page ii Tuesday June 27 2017 4 10 PM ...
Page 12: ...Freedom X Series INV Owners Guide book Page x Tuesday June 27 2017 4 10 PM ...
Page 14: ...Freedom X Series INV Owners Guide book Page ii Tuesday June 27 2017 4 10 PM ...
Page 22: ...Freedom X Series INV Owners Guide book Page 8 Tuesday June 27 2017 4 10 PM ...
Page 52: ...Freedom X Series INV Owners Guide book Page 38 Tuesday June 27 2017 4 10 PM ...
Page 81: ...Freedom X Series INV Owners Guide book Page i Tuesday June 27 2017 4 10 PM ...