recorded in the peak CO concentration.
Alarm Mode
1.
If the Initiating Unit is Triggered by CO:
When one CO alarm is triggered in the interconnected network, the unit will beep 4
times every 5.8 seconds, paired with the LED flashing red. Any other XC01-WR units
in the network will follow suit
—
they will beep 4 times every 5.8 seconds, paired with
the LED that flashes red 4 times first, followed by the LED that flashes green once
with every beep. When the CO concentration level drops below the alarm threshold,
the alarm will cease.
2.
If the Initiating Unit is Triggered by Smoke:
When one smoke alarm is triggered in the interconnected network, the unit will beep
3 times, paired with a red LED that flashes every 4 seconds. Any other XC01-WR
units will follow suit
—
they will beep 3 times every 4 seconds, paired with the LED
flashing red and green in succession.
NOTES
When one unit is triggered, other interconnected units will sound. If the smoke
alarm and CO alarm are triggered in the network at the same time, the alarm
signal of the smoke alarm will take priority over that of the CO alarm.
This alarm has a relay function that extends the wireless interconnected
network for wide detection coverage.
Silence Mode
Press the test button during an alarm to make the unit enter silence mode. If the CO
concentration still exceeds the alarm threshold, the unit will enter another alarm state.
Otherwise, the unit will exit the silence mode after 9 minutes and resume normal
operation. If the CO concentration is above 300 ppm, the silence function cannot be
enabled.
NOTES
1.
You can silence all interconnected units by pressing the Test/Silence button on
one of the units. If one unit is still alarming, it is the initiating unit (the unit that
detected danger); to silence all interlinked units, you must also press the
Test/Silence button on the initiating unit.
2.
While interconnected, the initiating unit cannot be triggered again during the
9-minute silence duration. However, all other interconnected units can be triggered