background image

appliances, or other possible sources of incomplete combustion. The installation of a smoke alarm is required for an 

early warning of fire. 

6.

 

CO alarms are not a substitute for life insurance. Though these CO alarms warn against increasing CO levels, we do 

not warrant or imply in any way that they will protect lives from CO poisoning. Homeowners and renters must still 

insure their lives. 

7.

 

CO alarms have a limited life. Although the CO alarm and all of its parts have passed many stringent tests and are 

designed  to  be  as  reliable  as  possible,  any  of  these  parts  could  fail  at  any  time.  Therefore,  you  are  strongly 

recommended to test your CO alarm weekly. 

8.

 

CO  alarms  are  not  foolproof.  Like  all  other  electronic  devices, CO  alarms  have  limitations.  They  can  only  detect 

CO that reaches their sensors. They may not give an early warning of rising CO levels if the CO is coming from a 

remote part of the house, or is at some distance from the CO alarm. 

 

Troubleshooting 

PROBLEM

 

SOLUTION

 

Your alarm does not sound during testing. 

 

Please ensure the batteries are properly installed in the 

alarm. 

 

Make sure you push thetest button firmly. 

 

Check the installation positioning. The wireless signal might 

be blocked or out of range. 

The yellow LED flashesonce every 60 seconds with one 

beep. 

The battery is low.

Replace the battery immediately.

 

The  yellow  LED  flashestwice  every60  seconds  with  2 

beeps. 

The alarm is malfunctioning. Please clean youralarm and see if it 

is working normally. If not, 

replace the device immediately.

 

The yellow LED flashes3 times every 60 seconds with 3 

beeps. 

The maximum lifetime (10 years) is reached. 

Replace the alarm 

immediately.

 If immediate replacement is not possible, you may 

push the TEST/HUSH button once to silence for 22 hours.

 

FCC Statement 

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC 

Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This 

equipment generates uses and can radiate radio frequency energy and, if not installed and used in accordance with the 

instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will 

not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which 

can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more 

Summary of Contents for Link+ CO03D-W

Page 1: ...X SENSE CO03D W Wireless Interlinked Carbon Monoxide Alarm...

Page 2: ...lectrochemical sensor designed for domestic use Please note that this device does not detect smoke heat flames or anyhazardous gas other than carbon monoxide even though carbonmonoxide can be generate...

Page 3: ...5 V AA Batteries 2 Screws 2 Anchor Plugs 1 User Manual 2 Carbon Monoxide Safety Stickers Product Features LCD Display Fault Low Battery Indicator Yellow LED Alarm Indicator Red LED Power Indicator Gr...

Page 4: ...programmed to sound an alarm at the following CO concentrations within the time periods listed 70 ppm for 60 240 minutes 150 ppm for 10 50 minutes and 400 ppm for 4 15 minutes When CO is detected and...

Page 5: ...22 hours by pressing the test button This end of life silence feature can only be used for a total of 30 days After 30 days the end of life signal cannot be silenced During this end of life silence p...

Page 6: ...nd make sure that they are both turned on to ensure successful connection NOTE Install the batteries correctly to turn on CO03D W To learn how to turn on different models of wireless interlinked alarm...

Page 7: ...NOTES 1 The alarm will enter the searching mode or the pairing mode for 60 seconds with the red LED flashing After 60 seconds repeat step 2 to connect the alarms If needed press the TEST HUSH button o...

Page 8: ...rm be tested during the weekly test Test a single CO alarm Test all interconnected CO alarms Action Press the TEST HUSH button Hold down theTEST HUSH button Indication The LCD will turn on and display...

Page 9: ...e appliance is in a room not normally used such as a boiler room the CO alarm should be placed just outside of this room so that the alarm can be heard more easily 1 Installing a CO Alarm in a Room wi...

Page 10: ...room with a fuel burning appliance Figure 1 In rooms with sloped ceilings the CO alarm should be located at the high side of the room 2 Installing the CO Alarm in a Bedroom or Room Without a Fuel Bur...

Page 11: ...y areas 2 Where there is the possibility of smoke or fumes under normal operating circumstances 3 In poorly ventilated kitchens garagesand furnace rooms Keep the CO alarms at least5 feet 1 5 m from po...

Page 12: ...rd the wall and the curved hole at the lower position 2 Mark 2 screw holes according to the holes on the mounting bracket then remove the bracket and drill the screw holes to a depth of 1 18 in 30 mm...

Page 13: ...sh 3 times sequentially every 1 5 seconds 3 long beeps every 1 5 seconds Dangeroussmoke concentration is detected by the initiating unit in the network Please find the initiating unit and take action...

Page 14: ...yellow LED indicator flashes 3 times every 60 seconds None Silence mode during the end of the cycle After 22 hours the unit will exit silence mode The green LED indicator flashes 3 times None Exiting...

Page 15: ...larm are triggered in the network at the same time the alarm signal of the smoke alarm will take priority over that of the CO alarm This alarm has a relay function that extends the wireless interconne...

Page 16: ...uated the area or has access to fresh air Do not re enter the house until it has been aired out and your alarm remains under normal condition If it is not possible to move outside stay close to an ope...

Page 17: ...detect CO that reaches the sensor CO may be present in other areas Doors or other obstructions may affect the rate at which CO reaches the CO alarm For this reason if bedroom doors are usually closed...

Page 18: ...ioning The wireless signal might be blocked or out of range The yellow LED flashesonce every 60 seconds with one beep The battery is low Replace the battery immediately The yellow LED flashestwice eve...

Page 19: ...equipment This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any int...

Reviews: