background image

8.

 

Where the air is turbulent, such as near ceiling fans, heat vents, air conditioner vents, fresh air return vents, or open 

windows. Excessive air flow may prevent any CO from reaching the sensors. 

9.

 

In direct sunlight. 

10.

 

Near large metal surfaces or where there are lots of cables or wires that can cause interference.   

11.

 

Near fluorescent lights, amateur radios, electrical equipment, or other units that may transmit an RF signal, as 

electronic noise can cause false alarms.   

 

Installation Method

 

NOTE: Before installation, it is recommended to test the interconnectedalarms in the rooms where you intend to 

install them to ensure that they are within transmission range and that nothing will interfere with their 

communication.   

1.

 

Twist to remove the mounting bracket. Hold the mounting bracket at the installation position with the flat side 

facing toward the wall and the curved hole at the lower position. 

2.

 

Mark 2 screw holes according to the holes on the mounting bracket, then remove the bracket and drill the screw 

holes to a depth of 1.18 in (30 mm) using a 1/4 in (Ø6.0 mm) drill bit. 

3.

 

Insert the anchor plugs into the holes, then tap them in with a hammer until their heads are flush with the wall.   

4.

 

Screw the mounting bracket to the wall using the provided screws or two 0.13 × 0.98 in (3.5 × 25 mm)countersunk 

screws. 

5.

 

Attach the alarm to the mounting bracket and tighten by twisting clockwise. 

6.

 

Test the unit by pressing the TEST/HUSH button. Ensure the unit sounds in an alarm pattern. 

 

LCD Display 

While detecting CO, the LCD will display different indicators to help you understand what to do, as shown below

 

 

Mode 

LCD Display

 

LED Indicator

 

Audible Alarm

 

Remarks

 

Powering On

 

 

Runs through 8 cycles 

(yellow/green/red indicator) in 

sequence. 

1 quick beep. 

 

 

Make sure the battery is 

installed correctly and the 

device is turned on.   

Standby Mode 

 

 

The green indicator flashes once 

every 60 seconds. 

None. 

None. 

Summary of Contents for Link+ CO03D-W

Page 1: ...X SENSE CO03D W Wireless Interlinked Carbon Monoxide Alarm...

Page 2: ...lectrochemical sensor designed for domestic use Please note that this device does not detect smoke heat flames or anyhazardous gas other than carbon monoxide even though carbonmonoxide can be generate...

Page 3: ...5 V AA Batteries 2 Screws 2 Anchor Plugs 1 User Manual 2 Carbon Monoxide Safety Stickers Product Features LCD Display Fault Low Battery Indicator Yellow LED Alarm Indicator Red LED Power Indicator Gr...

Page 4: ...programmed to sound an alarm at the following CO concentrations within the time periods listed 70 ppm for 60 240 minutes 150 ppm for 10 50 minutes and 400 ppm for 4 15 minutes When CO is detected and...

Page 5: ...22 hours by pressing the test button This end of life silence feature can only be used for a total of 30 days After 30 days the end of life signal cannot be silenced During this end of life silence p...

Page 6: ...nd make sure that they are both turned on to ensure successful connection NOTE Install the batteries correctly to turn on CO03D W To learn how to turn on different models of wireless interlinked alarm...

Page 7: ...NOTES 1 The alarm will enter the searching mode or the pairing mode for 60 seconds with the red LED flashing After 60 seconds repeat step 2 to connect the alarms If needed press the TEST HUSH button o...

Page 8: ...rm be tested during the weekly test Test a single CO alarm Test all interconnected CO alarms Action Press the TEST HUSH button Hold down theTEST HUSH button Indication The LCD will turn on and display...

Page 9: ...e appliance is in a room not normally used such as a boiler room the CO alarm should be placed just outside of this room so that the alarm can be heard more easily 1 Installing a CO Alarm in a Room wi...

Page 10: ...room with a fuel burning appliance Figure 1 In rooms with sloped ceilings the CO alarm should be located at the high side of the room 2 Installing the CO Alarm in a Bedroom or Room Without a Fuel Bur...

Page 11: ...y areas 2 Where there is the possibility of smoke or fumes under normal operating circumstances 3 In poorly ventilated kitchens garagesand furnace rooms Keep the CO alarms at least5 feet 1 5 m from po...

Page 12: ...rd the wall and the curved hole at the lower position 2 Mark 2 screw holes according to the holes on the mounting bracket then remove the bracket and drill the screw holes to a depth of 1 18 in 30 mm...

Page 13: ...sh 3 times sequentially every 1 5 seconds 3 long beeps every 1 5 seconds Dangeroussmoke concentration is detected by the initiating unit in the network Please find the initiating unit and take action...

Page 14: ...yellow LED indicator flashes 3 times every 60 seconds None Silence mode during the end of the cycle After 22 hours the unit will exit silence mode The green LED indicator flashes 3 times None Exiting...

Page 15: ...larm are triggered in the network at the same time the alarm signal of the smoke alarm will take priority over that of the CO alarm This alarm has a relay function that extends the wireless interconne...

Page 16: ...uated the area or has access to fresh air Do not re enter the house until it has been aired out and your alarm remains under normal condition If it is not possible to move outside stay close to an ope...

Page 17: ...detect CO that reaches the sensor CO may be present in other areas Doors or other obstructions may affect the rate at which CO reaches the CO alarm For this reason if bedroom doors are usually closed...

Page 18: ...ioning The wireless signal might be blocked or out of range The yellow LED flashesonce every 60 seconds with one beep The battery is low Replace the battery immediately The yellow LED flashestwice eve...

Page 19: ...equipment This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any int...

Reviews: