background image

Attaching Base Rails to Footings:

The previously assembled 
bearing block and 
vertical post assembly 
from step 3 are inserted 
into the sigma posts with 
the short vertical posts 
serving as the front and 
the longer vertical posts 
as the rear legs of the 
array.

The posts are aligned on 
site in accordance with 
the tilt angle of the rack; 
a minimum lapped joint 
length of 8 inches is needed for attachment.

The base rails (ST-AK 
182-120) are fastened to 
the bearing blocks with  
4 T-bolts assemblies 
attached by sliding head 
of the T-bolts into the two 
slots on to the bottom 
of the base rails (ST-AK 
182-120)on the eastwest 
axis. 

See Figure 5.1 

& 5.2

The T-Bolts must be 
turned 45° clockwise 
until they cannot be turned 
any further. 

See Figure 5.2

A line on the bottom of the 
T-bolts shows proper alignment. 
Line must be perpendicular to the 
rail. (Torque Hex nuts: 6 to 8 ft. 
lbs.) 

See Figure 5.3

To line up several system rails with one another, slide the splice halfway onto 
the assembled system rail.

Next, slide the other 
system rail onto the splice 
and push rails together 
until the rivet on the splice 
stops the movement. 
½” gap or separation 
between rails is required 
for thermal expansion. 

See Figures in 6.1, 
6.2 & 6.3

After the frame is complete the 
vertical post must be bolted to 
the sigma post with the supplied 
M10-120 mm hardware. The 
vertical posts can be moved 
vertically to achieve the required 
height and tilt angle of the 
array. When the correct angle 
is achieved a cordless drill with 
a 7/16 bit must be used to drill 
through the existing holes in 
the sigma post and through the 
aluminum vertical post before 
the hardware can be installed. 
Again, the vertical post must 
contact the sigma post for a 
minimum of 8 in. (200 mm).  
(Torque Hardware: 6 to 8 ft. lbs.) 

See Figures: 7.1, 7.2 & 7.3

Landscape Mode Framed PV Modules

ground-Mount application

Subject

 

to

 

technical

 

changes

   

 

Copyright

 

©

 

2009

 

HatiCon

 

Solar,

 

LLC

   

 

Page

 

3

 

of

 

9

 

 

Attaching

 

Base

 

Rails

 

to

 

Footings:

 

 

 

 

 

 

The

 

previously

 

assembled

 

bearing

 

block

 

and

 

vertical

 

post

 

assembly

 

from

 

step

 

3

 

are

 

inserted

 

into

 

the

 

sigma

 

posts

 

with

 

the

 

short

 

vertical

 

posts

 

serving

 

as

 

the

 

front

 

and

 

the

 

longer

 

vertical

 

posts

 

as

 

the

 

rear

 

legs

 

of

 

the

 

array.

   

 

The

 

posts

 

are

 

aligned

 

on

 

site

 

in

 

accordance

 

with

 

the

 

tilt

 

angle

 

of

 

the

 

rack;

 

a

 

minimum

 

lapped

 

joint

 

length

 

of

 

8

 

inches

 

is

 

needed

 

for

 

attachment.

  

 

 

 

 

 

 

 

 

The

 

base

 

rails

 

(ST

AK

 

182

120)

 

are

 

fastened

 

to

 

the

 

bearing

 

blocks

 

with

 

4

 

T

bolts

 

assemblies

 

attached

 

by

 

sliding

 

head

 

of

 

the

 

T

bolts

 

into

 

the

 

two

 

slots

 

on

 

to

 

the

 

bottom

 

of

 

the

 

base

 

rails

 

(ST

AK

 

182

120)on

 

the

 

east

west

 

axis.

   

See

 

Figure

 

5.1

 

&

 

5.2

 

 

 

 

The

 

T

Bolts

 

must

 

be

 

turned

 

45°

 

clockwise

 

until

 

they

 

cannot

 

be

 

turned

 

any

 

further.

 

See

 

Figure

 

5.2

 

 

 

 

 

 

 

A

 

line

 

on

 

the

 

bottom

 

of

 

the

 

T

bolts

 

shows

 

proper

 

alignment.

 

Line

 

must

 

be

 

perpendicular

 

to

 

the

 

rail.

 

(

Torque

 

Hex

 

nuts:

 

6

 

to

 

8

 

ft.

 

lbs.)

 

See

 

Figure

 

5.3

 

 

 

 

 

 

 

 

 

 

 

 

 

4.1

4.2

 

5.3

 

5.1

5.2

 

12

 

in.

 

Minimum

 

  12 in. Minimum

Fig. 4.1

Fig. 4.2

Subject

 

to

 

technical

 

changes

   

 

Copyright

 

©

 

2009

 

HatiCon

 

Solar,

 

LLC

   

 

Page

 

3

 

of

 

9

 

 

Attaching

 

Base

 

Rails

 

to

 

Footings:

 

 

 

 

 

 

The

 

previously

 

assembled

 

bearing

 

block

 

and

 

vertical

 

post

 

assembly

 

from

 

step

 

3

 

are

 

inserted

 

into

 

the

 

sigma

 

posts

 

with

 

the

 

short

 

vertical

 

posts

 

serving

 

as

 

the

 

front

 

and

 

the

 

longer

 

vertical

 

posts

 

as

 

the

 

rear

 

legs

 

of

 

the

 

array.

   

 

The

 

posts

 

are

 

aligned

 

on

 

site

 

in

 

accordance

 

with

 

the

 

tilt

 

angle

 

of

 

the

 

rack;

 

a

 

minimum

 

lapped

 

joint

 

length

 

of

 

8

 

inches

 

is

 

needed

 

for

 

attachment.

  

 

 

 

 

 

 

 

 

The

 

base

 

rails

 

(ST

AK

 

182

120)

 

are

 

fastened

 

to

 

the

 

bearing

 

blocks

 

with

 

4

 

T

bolts

 

assemblies

 

attached

 

by

 

sliding

 

head

 

of

 

the

 

T

bolts

 

into

 

the

 

two

 

slots

 

on

 

to

 

the

 

bottom

 

of

 

the

 

base

 

rails

 

(ST

AK

 

182

120)on

 

the

 

east

west

 

axis.

   

See

 

Figure

 

5.1

 

&

 

5.2

 

 

 

 

The

 

T

Bolts

 

must

 

be

 

turned

 

45°

 

clockwise

 

until

 

they

 

cannot

 

be

 

turned

 

any

 

further.

 

See

 

Figure

 

5.2

 

 

 

 

 

 

 

A

 

line

 

on

 

the

 

bottom

 

of

 

the

 

T

bolts

 

shows

 

proper

 

alignment.

 

Line

 

must

 

be

 

perpendicular

 

to

 

the

 

rail.

 

(

Torque

 

Hex

 

nuts:

 

6

 

to

 

8

 

ft.

 

lbs.)

 

See

 

Figure

 

5.3

 

 

 

 

 

 

 

 

 

 

 

 

 

4.1

4.2

 

5.3

 

5.1

5.2

 

12

 

in.

 

Minimum

 

Subject

 

to

 

technical

 

changes

   

 

Copyright

 

©

 

2009

 

HatiCon

 

Solar,

 

LLC

   

 

Page

 

3

 

of

 

9

 

 

Attaching

 

Base

 

Rails

 

to

 

Footings:

 

 

 

 

 

 

The

 

previously

 

assembled

 

bearing

 

block

 

and

 

vertical

 

post

 

assembly

 

from

 

step

 

3

 

are

 

inserted

 

into

 

the

 

sigma

 

posts

 

with

 

the

 

short

 

vertical

 

posts

 

serving

 

as

 

the

 

front

 

and

 

the

 

longer

 

vertical

 

posts

 

as

 

the

 

rear

 

legs

 

of

 

the

 

array.

   

 

The

 

posts

 

are

 

aligned

 

on

 

site

 

in

 

accordance

 

with

 

the

 

tilt

 

angle

 

of

 

the

 

rack;

 

a

 

minimum

 

lapped

 

joint

 

length

 

of

 

8

 

inches

 

is

 

needed

 

for

 

attachment.

  

 

 

 

 

 

 

 

 

The

 

base

 

rails

 

(ST

AK

 

182

120)

 

are

 

fastened

 

to

 

the

 

bearing

 

blocks

 

with

 

4

 

T

bolts

 

assemblies

 

attached

 

by

 

sliding

 

head

 

of

 

the

 

T

bolts

 

into

 

the

 

two

 

slots

 

on

 

to

 

the

 

bottom

 

of

 

the

 

base

 

rails

 

(ST

AK

 

182

120)on

 

the

 

east

west

 

axis.

   

See

 

Figure

 

5.1

 

&

 

5.2

 

 

 

 

The

 

T

Bolts

 

must

 

be

 

turned

 

45°

 

clockwise

 

until

 

they

 

cannot

 

be

 

turned

 

any

 

further.

 

See

 

Figure

 

5.2

 

 

 

 

 

 

 

A

 

line

 

on

 

the

 

bottom

 

of

 

the

 

T

bolts

 

shows

 

proper

 

alignment.

 

Line

 

must

 

be

 

perpendicular

 

to

 

the

 

rail.

 

(

Torque

 

Hex

 

nuts:

 

6

 

to

 

8

 

ft.

 

lbs.)

 

See

 

Figure

 

5.3

 

 

 

 

 

 

 

 

 

 

 

 

 

4.1

4.2

 

5.3

 

5.1

5.2

 

12

 

in.

 

Minimum

 

Fig. 5.1

Fig. 5.2

Fig. 5.3

Subject

 

to

 

technical

 

changes

   

 

Copyright

 

©

 

2009

 

HatiCon

 

Solar,

 

LLC

   

 

Page

 

4

 

of

 

9

 

 

 

 

To

 

line

 

up

 

several

 

system

 

rails

 

with

 

one

 

another,

 

slide

 

the

 

splice

 

halfway

 

onto

 

the

 

assembled

 

system

 

rail.

 

 

 

 

Next,

 

slide

 

the

 

other

 

system

 

rail

 

onto

 

the

 

splice

 

and

 

push

 

rails

 

together

 

until

 

the

 

rivet

 

on

 

the

 

splice

 

stops

 

the

 

movement.

 

½”

 

gap

 

or

 

separation

 

between

 

rails

 

is

 

required

 

for

 

thermal

 

expansion.

 

See

 

Figures

 

in

 

6.1,

 

6.2

 

&

 

6.3

 

 

 

Note:

 Do not attempt to through bolt any splices. 

The splice was designed to allow the aluminum rails 

to expand and contract under thermal conditions. 

 

 

 

 

 

 

 

 

 

After

 

the

 

frame

 

is

 

complete

 

the

 

vertical

 

post

 

must

 

be

 

bolted

 

to

 

the

 

sigma

 

post

 

with

 

the

 

supplied

 

M10

120

 

mm

 

hardware.

 

The

 

vertical

 

posts

 

can

 

be

 

moved

 

vertically

 

to

 

achieve

 

the

 

required

 

height

 

and

 

tilt

 

angle

 

of

 

the

 

array.

 

When

 

the

 

correct

 

angle

 

is

 

achieved

 

a

 

cordless

 

drill

 

with

 

a

 

7/16

 

bit

 

must

 

be

 

used

 

to

 

drill

 

through

 

the

 

existing

 

holes

 

in

 

the

 

sigma

 

post

 

and

 

through

 

the

 

aluminum

 

vertical

 

post

 

before

 

the

 

hardware

 

can

 

be

 

installed.

 

Again,

 

the

 

vertical

 

post

 

must

 

contact

 

the

 

sigma

 

post

 

for

 

a

 

minimum

 

of

 

8

 

in.

 

(200

 

mm).

  

(Torque

 

Hardware:

 

6

 

to

 

8

 

ft.

 

lbs.)

 

See

 

Figures:

 

7.1,

 

7.2

 

&

 

7.3

 

 

 

 

 

 

 

 

 

 

6.2

 

7.2

 

Note: 

Do not attempt to through-bolt any splices. The splice was  
designed to allow the aluminum rails to expand and contract  
under thermal conditions.

Fig. 6.1

Fig. 6.2

Fig. 6.3

Subject

 

to

 

technical

 

changes

   

 

Copyright

 

©

 

2009

 

HatiCon

 

Solar,

 

LLC

   

 

Page

 

4

 

of

 

9

 

 

 

 

To

 

line

 

up

 

several

 

system

 

rails

 

with

 

one

 

another,

 

slide

 

the

 

splice

 

halfway

 

onto

 

the

 

assembled

 

system

 

rail.

 

 

 

 

Next,

 

slide

 

the

 

other

 

system

 

rail

 

onto

 

the

 

splice

 

and

 

push

 

rails

 

together

 

until

 

the

 

rivet

 

on

 

the

 

splice

 

stops

 

the

 

movement.

 

½”

 

gap

 

or

 

separation

 

between

 

rails

 

is

 

required

 

for

 

thermal

 

expansion.

 

See

 

Figures

 

in

 

6.1,

 

6.2

 

&

 

6.3

 

 

 

Note:

 Do not attempt to through bolt any splices. 

The splice was designed to allow the aluminum rails 

to expand and contract under thermal conditions. 

 

 

 

 

 

 

 

 

 

After

 

the

 

frame

 

is

 

complete

 

the

 

vertical

 

post

 

must

 

be

 

bolted

 

to

 

the

 

sigma

 

post

 

with

 

the

 

supplied

 

M10

120

 

mm

 

hardware.

 

The

 

vertical

 

posts

 

can

 

be

 

moved

 

vertically

 

to

 

achieve

 

the

 

required

 

height

 

and

 

tilt

 

angle

 

of

 

the

 

array.

 

When

 

the

 

correct

 

angle

 

is

 

achieved

 

a

 

cordless

 

drill

 

with

 

a

 

7/16

 

bit

 

must

 

be

 

used

 

to

 

drill

 

through

 

the

 

existing

 

holes

 

in

 

the

 

sigma

 

post

 

and

 

through

 

the

 

aluminum

 

vertical

 

post

 

before

 

the

 

hardware

 

can

 

be

 

installed.

 

Again,

 

the

 

vertical

 

post

 

must

 

contact

 

the

 

sigma

 

post

 

for

 

a

 

minimum

 

of

 

8

 

in.

 

(200

 

mm).

  

(Torque

 

Hardware:

 

6

 

to

 

8

 

ft.

 

lbs.)

 

See

 

Figures:

 

7.1,

 

7.2

 

&

 

7.3

 

 

 

 

 

 

 

 

 

 

6.2

 

7.2

 

Fig. 7.1

Fig. 7.2

Fig. 7.3

Assembly Instructions 

16

Solar 

Mounting Sytem

Summary of Contents for Framed PV

Page 1: ...Solar Mounting System Assembly Instructions...

Page 2: ......

Page 3: ...n sliding the rear post vertically until the next adjustment hole is visible through the hole in which the bolt was removed Fasten all triangles at desired tilt angle Framed Modules portrait Framed Mo...

Page 4: ...bject to technical changes Copyright 2009 HatiCon Solar LLC Page Assembly sequence of the flat roof First the angle brackets must be assembled b fastening T Bolt nut and washer Hardware m remain loose...

Page 5: ...of 11 Installing Triangles Triangles can now be mounted to base rails To do this properly space triangles on the base rail per the structural site specific drawings and attach with cross adapters A to...

Page 6: ...6 1 One of these is mounted for each completed row and at least one for every 40 ft The diagonal straps are fastened to the rear triangle struts using T Bolts See Figure 6 2 Torque 6 to 8 ft lbs Insta...

Page 7: ...s Clamps should be attached of the way down from the edge of the module See Figure 9 2 Then slide the module into the thin film end clamp and tighten the T Bolts clockwise Torque 6 to 8 ft lbs Next sl...

Page 8: ...g instructions reflect the state of technology and our experience on how to install our systems on site Due to the fact that each roof has individual characteristics we highly recommend commissioning...

Page 9: ...can be attached using a splice To install simply insert the splice into the end of the rail that will need to be joined until the rivet on the middle of the splice stops the insertion Then slide the o...

Page 10: ...click the mid clamp onto the mounting rail an slide it onto the module Ensure that the mid clam clicks onto both sides of the mounting rail See Figure 4 2 Now slide the next module under the mid clam...

Page 11: ...the horizontal substrate rails for each row of modules using the cross adapters Click the cross adapters onto the base rails and slide attachment lip into channel on base rail Fasten the clamp screws...

Page 12: ...uring installation If a concrete foundation is prepared the sinking of the sigma posts with rebar requires a reinforced foundation A hole must be drilled within 8 inches of the bottom of the sigma pos...

Page 13: ...nges Copyright 2009 HatiCon Solar LLC Page 3 of 8 The previously assembled bearing block and vertical post assembly from step 3 are inserted into the sigma posts with the short vertical posts serving...

Page 14: ...ardware ST AK 120 90 Mounting Rail ST AK 120 90 Splice ST AK 60 37 Mounting Rail ST AK 60 37 Splice ST AK 66 37 Mounting Rail ST AK 66 37 Splice The designs are based on the following codes 2006 Inter...

Page 15: ...side of bearing block must face thin side of vertical post profile to maintain structural Integrity See Figures 3 1 and 3 2 Nut and washer must be fastened on the thick side of the vertical post extru...

Page 16: ...est axis See Figure 5 1 5 2 The T Bolts must be turned 45 clockwise until they cannot be turned any further See Figure 5 2 A line on the bottom of the T bolts shows proper alignment Line must be perpe...

Page 17: ...ils and slide attachment lip into channel of base rail on either side See Figures 7 1 7 2 Fasten the clamp screws by turning clockwise Torque to 6 to 8 ft Lbs ST AK 60 37 7 1 7 2 Fig 8 1 Fig 8 2 Subje...

Page 18: ...f a column of landscape oriented modules See Figure 10 3 Once the module is mounted click the mid clamp onto the module rail and slide the clamp onto the module frame See Figure 10 4 10 4 10 3 Adjusta...

Page 19: ......

Page 20: ...W rth Canada Limited Limit e 6330 Tomken Road Mississauga Ontario Canada L5T 1N2 Tel 905 564 6225 Fax 905 564 3671 www wurthcanada com...

Reviews: