ANI-1F3
8
ANI-1F3_V2.0.0_PI_2021-04_EN
Subject to technical changes
FRIGOLINK
Analogue inputs S 1 - S 16
* The outside temperature is sent over the CAN bus system.
NOTICE
•
Terminals 193/194 cannot be wired, they are empty.
Terminal
Sensor input
Sensor type
Assignment
161/162
S 1
TRK
Suction gas tempera-
ture MT rack
163/164
S 2
DGF
Hot gas temperature
MT rack
165/166
S 3
DGF
Desuperheating tem-
perature LT compres-
sor
167/168
S 4
TRK
Outside temperature
*
169/170
S 5
DGF
Gas cooler outlet
temperature / T.gc 1
171/172
S 6
DGF
Gas cooler outlet
temperature / T.gc 2
173/174
S 7
DGF
Outlet temperature
HR CO2
175/176
S 8
DGF
Outlet temperature
HR medium
177/178
S 9
DGF
Input temperature HR
medium
179/180
S 10
-
Not available
181/182
S 11
-
Not available
183/184
S 12
TRK
Suction gas tempera-
ture LT
185/186
S 13
DGF
Gas cooler outlet
temperature in front
of HPV
187/188
S 14
TRK
HP suction gas tem-
perature
189/190
S 15
TRK
HP defrost tempera-
ture
191/192
S 16
TRK
Control cabinet sen-
sor