![WURM FRIGOLINK ANI-1F3 Manual Download Page 7](http://html1.mh-extra.com/html/wurm/frigolink-ani-1f3/frigolink-ani-1f3_manual_1000998007.webp)
ANI-1F3
ANI-1F3_V2.0.0_PI_2021-04_EN
7
Subject to technical changes
FRIGOLINK
Analogue inputs Uin 1, 2
Analogue inputs Iin 1 - Iin 5
125
DI 15
230V~
Max. refrigerant fault
135
N
126
DI 16
230V~
LP rack fault
136
N
127
DI 17
230V~
HP rack fault
137
N
128
DI 18
230V~
GC fan fault
138
N
129
DI 19
230V~
Alarm input 1 (NC)
139
N
130
DI 20
230V~
Alarm input 2 (NC)
140
N
Terminal
Analogue input
Potential
Assignment
41
Uin 1
GND
Not available
42
0...10V
43
Uin 2
GND
Not available
44
0...10V
Terminal
Analogue input
Potential
Assignment
151
Iin 1
4...20mA
p0 - MT 1
152
24V=
153
Iin 2
4...20mA
p.mp
154
24V=
155
Iin 3
4...20mA
p.gc
156
24V=
157
Iin 4
4...20mA
p0 - LT
158
24V=
159
Iin 5
4...20mA
p0 - MT 2 / heat pump
160
24V=
Terminal
Digital input
Potential
Assignment