WURM FRIGOLINK ANI-1F3 Manual Download Page 12

ANI-1F3

12

 ANI-1F3_V2.0.0_PI_2021-04_EN

Subject to technical changes

FRIGOLINK

1.4.4 

FIO001B/FIO-PAT circuit diagram

Fig. 6: FIO-PAT circuit diagram

Address 0 - extended HR

NOTICE

Always select address 0 for FIO001B/FIO-PAT.

Terminal

Sensor input

Sensor type

Assignment

16/17

S 1

Not available

14/15

S 2

TRK

Shop temperature

11/12/13

S 3

4...20mA

Water pressure

Terminal

Input

Assignment

21/22

DI 1

Gas cooler bypass valve open

21/23

DI 2

Gas cooler bypass valve closed

21/24

DI 3

HR valve open

21/25

DI 4

HR valve closed

21/26

DI 5

HR pump fault

21/27

DI 6

Heat pump blocking

21/28

DI 7

LT compressor 2 operating feedback

21/29

DI 8

LT compressor 2 fault

Terminal

Output

Assignment

18/19

Aout

0...10V HR/air con. pump

32/33

K 1

Defrost HP

34/35

K 2

External heating enable

36/37

K 3

Water pipe heating

38/39

K 4

LT compressor 2 enable

18 19

0

0

27 26 25 24 23 22 21

28

29

17

16

15

14

13

12

11

37 36 35 34 33 32 31

38

39

!

Frigolink

FIO 001 PAT

Ein-/Ausgabe

A out

GND

GND

E

S3

4-20 mA

S2

Fühler 2

S1

Fühler 1

+U 

B

K3

K1

K2

N

K4

0-10V

CAN Tx

CAN Rx

DI 1

DI 3

DI 5

DI 7

DI 2

DI 4

DI 6

DI 8

Digitale Eingänge 230V~

CAN-BUS

Modul Nr.

230V~

12

11

13

14

15

16

17

18

29

28

27

26

25

23

24

22

21

19

38

39

34

35

36

37

33

32

31

Summary of Contents for FRIGOLINK ANI-1F3

Page 1: ...compressor fault 3 step load shedding including Fastreturn Operating hours counter and cycle counter for each compressor Proactive oil return High pressure and medium pressure control Gas cooler fan c...

Page 2: ...S 16 8 1 4 2 Output circuit diagram 9 Digital outputs relays K 1 K 14 9 Digital outputs SSR V 1 V 4 10 Analogue outputs Uout 1 Uout 5 10 1 4 3 Communication circuit diagram 11 Communication 11 1 4 4...

Page 3: ...NG DANGER TO LIFE FROM ELECTRIC SHOCK AND OR FIRE Switch off the power to the entire plant when carrying out installation wiring or removal work Otherwise a mains voltage and or external voltage may s...

Page 4: ...r individual projects and are not described in detail in this document This document automatically ceases to be valid if a new technical description is issued Manufacturer Wurm GmbH Co KG Elektronisch...

Page 5: ...V Analog Input Uin 1 2 4 20mA Analog Input Iin 1 5 Digital Inputs DI 1 20 230V 50Hz 140 130 N 20 11 neutral terminal DI 10 1 230V 120 110 131 121 111 101 DI 20 11 230V N 10 1 neutral terminal N 230V 1...

Page 6: ...Digital Inputs DI 1 20 230V 50Hz 140 130 N 20 11 neutral terminal DI 10 1 230V 120 110 131 121 111 101 DI 20 11 230V N 10 1 neutral terminal N 230V 101 110 121 130 111 120 131 140 N max 20VA ANIMUS A...

Page 7: ...n fault 138 N 129 DI 19 230V Alarm input 1 NC 139 N 130 DI 20 230V Alarm input 2 NC 140 N Terminal Analogue input Potential Assignment 41 Uin 1 GND Not available 42 0 10V 43 Uin 2 GND Not available 44...

Page 8: ...perature LT compres sor 167 168 S 4 TRK Outside temperature 169 170 S 5 DGF Gas cooler outlet temperature T gc 1 171 172 S 6 DGF Gas cooler outlet temperature T gc 2 173 174 S 7 DGF Outlet temperatur...

Page 9: ...DI 1 20 230V 50Hz 140 130 N 20 11 neutral terminal DI 10 1 230V 120 110 131 121 111 101 DI 20 11 230V N 10 1 neutral terminal N 230V 101 110 121 130 111 120 131 140 N max 20VA ANIMUS ANI 1F3 part of F...

Page 10: ...A 230V NO HG bypass 232 COM 233 Semiconductor V 2 4 60VA 230V NO Post injection PWM 234 COM 235 Semiconductor V 3 4 60VA 230V NO HP evaporator EEV PWM 236 COM 237 Semiconductor V 4 4 60VA 230V NO Valv...

Page 11: ...4 2 A 230V 211 201 210 K 1 4 each 4 2 A 230V 220 K 10 14 each 4 2 A 230V 221 230 S16 194 S 15 11 Sensor 190 191 181 S 10 6 Sensor 180 171 170 S 5 1 Sensor 161 Iin 1 5 4 20mA 160 151 Uin 2 1 0 10V 44 4...

Page 12: ...R valve closed 21 26 DI 5 HR pump fault 21 27 DI 6 Heat pump blocking 21 28 DI 7 LT compressor 2 operating feedback 21 29 DI 8 LT compressor 2 fault Terminal Output Assignment 18 19 Aout 0 10V HR air...

Page 13: ...t available Terminal Input Assignment 36 39 DI 1 Flow monitor 37 39 DI 2 Frost protection 38 39 DI 3 Air conditioning request Terminal Output Assignment 41 42 Aout 1 0 10V HP evaporator EEV 42 43 Aout...

Page 14: ...2 Not available 38 39 DI 3 Not available Terminal Output Assignment 41 42 Aout 1 0 10V GC bypass 42 43 Aout 2 0 10V IHE valve 18 19 K 1 IHE oil valve 16 17 K 2 Not available 14 15 K 3 Not available T...

Page 15: ...off Top hat rail installation 1 There are 2 fastening safety catches located on the back of the module A Press both fastening safety catches a downward until they engage with a click 2 There are 4 ret...

Page 16: ...x DGF TRK C BUS communication 3 wire CAN bus interface shielded galvanically isolated screw ter minals 2 5mm2 and RJ45 socket for communicating with system devices F BUS communication 3 wire CAN bus...

Reviews: