Fault messages and emergency programs 

In case of a fault, the display flashes with the fault code. 

Display 

Cause 

Monitoring function and emergency program 

COLL

 

Address conflict on CAN bus 

The set module number is already assigned. 
Set a different module number! 

buS 

 

CAN bus error 
No communication over the CAN 
bus 

Check the CAN bus connection! 

ErCo

  CAN bus communication error 

The device has detected activities on the field bus, 
but is not being controlled by the corresponding 
master module. Check address setting and 
parameter settings of the master module! 

 EE 

 

Data fault in non-volatile memory A power surge may destroy the set parameters. 

Operation is carried out with the factory default 
settings. Newly enter all storage locations! De-
energise the control unit! 

 

7 Technical 

data 

Power supply 

Through transformer TR9-9-4 with plug connection 

Communication 

3-wire CAN bus interface, galvanically isolated 

Temperature sensor 

3 x TRK277/5ST-PLUS or TRK277/7ST-PLUS 
(Standard connection: supply air, return air, defrost limit) 
1 x TRK-EEV/7ST (suction gas) 

Analogue input 

4…20mA, output voltage 18V=, max. 22mA 

Digital inputs 

3 x potential-free contact 
(1 x cold location off, 1 x 2nd setpoint, 1 x cold room door open) 

Outputs 

The total current on the output relays and electronic relay must not 
exceed 6A. 

Output relay 

1 x cooling, normally closed contact, 230V~, 3(2)A 
1 x fan, normally closed contact, 230V~, 3(2)A 
1 x defrost, normally open contact, 230V~, 3(2)A 

Electronic 

semiconductor relay 

1 x control of a pulse-width modulated EEV, 230V~, 4…60VA, note the 
minimum power output! 

 Residual voltage measureable! Integrated semiconductor 

protection (no isolator) 

Analogue output 

1 x 0…10V=, non-isolated, max. load 1mA 
Alternatively for control of an electronic relay ATV230 (valve 230V~/=) 

Housing 

Plastic 

Dimensions 

(WxHxD) 158 x 32 x 75mm 

Fastening 

In the installation cut-out with holding clips and sealing frame (120 x 
28mm) 

Ambient temperature 

Operation: 0...+55°C, storage: -25…+70°C 

Degree of protection 

IP54 (front) 

Weight 

About 150g 

CE conformity 

  2014/30/EU (EMC Directive) 

  2014/35/EU (Low Voltage Directive)  

 

EAC conformity 

  TR CU 004/2011 

  TR CU 020/2011 

 

 

RoHS II 

Valid from 

Version 2.2 

 

 

Note! 

 

Please observe the detailed descriptions in the chapters of the FRIGOLINK system manual.

 

Summary of Contents for FKE003

Page 1: ...ctronic relay valve controller 230V or ATV230 valve actuation 230V Control of one evaporator per module Integrated temperature display Tool free front installation Fixed input output allocation for se...

Page 2: ...ric shock and or fire Switch off the power to the entire plant when installing wiring or removing Otherwise a mains voltage and or external voltage may still be present even if the control voltage is...

Page 3: ...rol elements 5 4 Device operation 5 4 1 Activating the advanced level 5 4 2 Selecting parameters 5 4 3 Set parameter 6 4 4 Set module number 6 4 5 Block keys against unauthorised operation 6 5 Paramet...

Page 4: ...for the FKE003 Cables Application ZCB C TR 0 6 Controller transformer 0 6m ZCB C TR 2 0 Controller transformer 2 0m ZCB C REL2M 5P Controller load 5 pin ZCB C DI 2 0 Controller digital inputs 2 0m ZC...

Page 5: ...Advanced level will flash for as long as the level is released P P 5s 2 To return to the advanced level press the P key again for 5 seconds If no key is pressed within 2 minutes the display automatic...

Page 6: ...ed within 2 minutes the display automatically returns to the standard level and parameter change is disabled The jump back is always made to the temperature display 4 4 Set module number For easier se...

Page 7: ...ure of suction gas sensor S4 P05 Actual value 4 20mA 0 25 5 Current on 4 20mA input resolution 0 25 5mA P06 Actual value 0 10V output 0 100 Triggering of the 0 10V output resolution 0 100 P07 Sensor t...

Page 8: ...d connection supply air return air defrost limit 1 x TRK EEV 7ST suction gas Analogue input 4 20mA output voltage 18V max 22mA Digital inputs 3 x potential free contact 1 x cold location off 1 x 2nd s...

Reviews: