When keys are blocked, each time a key is pressed, the access and advanced level LEDs are lit to 
indicate that key blocking is active, so that the device will not be considered faulty mistake. 

 

 

The block can be removed by pressing the service key together with the Menu key "

P

" for 5 seconds. 

Removal of the block is signalled by the appearance of the text "

FrEE

" for 1 second. 

 

5 Parameter 

Standard level: actual value 

No. 

Parameter 

factory 

Min. 

Max.  Description 

P00 

Control actual value 

 

Current actual value of temperature control 

 

 

 

 

 

 

Advanced level: actual values and setpoints 

No. 

Parameter 

factory 

Min. 

Max.  Description 

P01 

Actual value of supply air 

 

Temperature of supply air sensor S1 

P02 

Actual value of return air 

 

Temperature of return air sensor S2 

P03 

Actual value of defrost limit 
sensor 

 

Temperature of defrost limit sensor S3 

P04 

Actual value of suction gas 
temperature 

 

Temperature of suction gas sensor S4 

P05 

Actual value 4...20mA  

 

25.5 

Current on 4…20mA input (resolution: 0...25.5mA) 

P06 

Actual value 0...10V output 

 

100 

Triggering of the 0...10V output (resolution: 0...100%) 

P07 

Sensor type supply air S1 

277 

Type of the temperature sensor – to be set on the master 
module 

P08 

Sensor type return air S2 

277 

Type of the temperature sensor – to be set on the master 
module 

P09 

Sensor type defrost limit S3 

277 

Type of the temperature sensor – to be set on the master 
module 

P10 

Sensor type suction gas 
temperature S4 

277 

Type of the temperature sensor – to be set on the master 
module 

P11

*

  Address 

Selected module number (F-BUS address) 

P12 

Version 

 

Applied device version 

P13

*

  Relay test function 

 

0 = all relays off 
1 = defrost 
2 = cooling 
3 = fan 
The relay test is automatically deactivated if the menu is 
exited or if there is no other key input for 2 minutes. 

P14 

Status of input: cold location 
off 

OFF 

OFF  ON 

Current status of digital input DI1 

P15 

Status of input: 2n setpoint 

OFF 

OFF  ON 

Current status of digital input DI2 

P16 

Status of input: Door open 

OFF 

OFF  ON 

Current status of digital input DI3 

*

Adjustable parameters

 

 

 

Note! 

 5s Service key + 

P

  => keys enabled 

Summary of Contents for FKE003

Page 1: ...ctronic relay valve controller 230V or ATV230 valve actuation 230V Control of one evaporator per module Integrated temperature display Tool free front installation Fixed input output allocation for se...

Page 2: ...ric shock and or fire Switch off the power to the entire plant when installing wiring or removing Otherwise a mains voltage and or external voltage may still be present even if the control voltage is...

Page 3: ...rol elements 5 4 Device operation 5 4 1 Activating the advanced level 5 4 2 Selecting parameters 5 4 3 Set parameter 6 4 4 Set module number 6 4 5 Block keys against unauthorised operation 6 5 Paramet...

Page 4: ...for the FKE003 Cables Application ZCB C TR 0 6 Controller transformer 0 6m ZCB C TR 2 0 Controller transformer 2 0m ZCB C REL2M 5P Controller load 5 pin ZCB C DI 2 0 Controller digital inputs 2 0m ZC...

Page 5: ...Advanced level will flash for as long as the level is released P P 5s 2 To return to the advanced level press the P key again for 5 seconds If no key is pressed within 2 minutes the display automatic...

Page 6: ...ed within 2 minutes the display automatically returns to the standard level and parameter change is disabled The jump back is always made to the temperature display 4 4 Set module number For easier se...

Page 7: ...ure of suction gas sensor S4 P05 Actual value 4 20mA 0 25 5 Current on 4 20mA input resolution 0 25 5mA P06 Actual value 0 10V output 0 100 Triggering of the 0 10V output resolution 0 100 P07 Sensor t...

Page 8: ...d connection supply air return air defrost limit 1 x TRK EEV 7ST suction gas Analogue input 4 20mA output voltage 18V max 22mA Digital inputs 3 x potential free contact 1 x cold location off 1 x 2nd s...

Reviews: