7-13
Alarm Configuration
7.6. The Power Cycle Alarm
The Power Cycle Alarm can provide notification when all input power to the RSM-8R unit
is lost and then restored. When the power supply is lost and then restored, the RSM-8R
can provide notification via Email, Syslog Message or SNMP Trap.
Notes:
• The Power Cycle alarm can provide notification when all input power to the
RSM-8R unit is lost and then restored. This alarm will not function when
only one power input line is disconnected. To provide notification when one
power input line is lost or disconnected, please use the Lost Voltage (Line In)
Alarm as described in Section 7.9.
• In order for the RSM-8R to provide alarm notification via Email,
communication parameters must first be defined as described in
Section 5.9.11.
• In order for the RSM-8R to provide alarm notification via Syslog Message,
Syslog parameters must first be defined and Syslog Messages must be
enabled as described in Section 5.9.2 and Section 11.
• In order for the RSM-8R to provide alarm notification via SNMP Trap, SNMP
parameters must first be defined, and SNMP Traps must be enabled as
described in Section 5.9.7 and Section 12.
To configure the Power Cycle Alarm, you must access the RSM-8R command mode
using a password that permits Administrator Level commands. The Power Cycle Alarm
configuration menu offers the following parameters:
•
Trigger Enable:
Enables/Disables the trigger for this alarm. When Disabled, this
alarm will be suppressed. (Default = On.)
•
Email Message:
Enables/Disables email notification for this alarm. (Default = On.)
Note:
The Email Message parameter offers four different options: On, Off, On
(Copy to All Triggers) or Off (Copy to All Triggers). If either of the "Copy to All
Triggers" options is selected, then email notification for all other alarms will be
switched On or Off as indicated by this parameter. For example, If "Off (Copy
to All Triggers)" is selected, then Email notification will be disabled for all other
alarms too.
•
Address 1, 2, and 3:
These parameters are used to select which of the three email
addresses defined via the "Email Messages" menu (see Section 5.9.11) will receive
the email alarm notification messages generated by this alarm. The Address
parameters can be used to select one, or any combination of the addresses defined
via the Email Messages menu. (Default = All On.)
Note:
If Email addresses have been previously specified, then the text under
the parameters will list the current, user defined email addresses.
•
Subject:
This parameter is used to define the text that will appear in the "Subject"
field for all email notification messages generated by this alarm. (Default = "Alarm:
Power Cycle")