9.2.3 Cleaning of Cooling Air Inlet and Cooling Air Outlet
The covers are connected with the PE conductor to the cabinet.
Maintenance Tasks:
1.
See
Section 8.1.1
9.2.4 Torque Check of Electrical Connections
Maintenance Tasks:
1.
Check
connections and connectors of all parts for tight fit.
If connections are loose,
contact
customer service
for specific
torque.
Tighten
with specific torque.
2.
Check
the grounding connection (Section 5.5.1.1), AC connection
(Section 5.5.1.2) and DC connection (Section 5.5.1.3) for tight fit.
If connections is loose,
tighten
with shown torque (Table 12).
3.
Check
the insulation and electrical connections for discoloration and
corrosion.
In case of discoloration and corrosion,
renew
the connection
immediately.
Tighten
with specific or shown torque (Table 12).
Table 12: Torque of electrical connections
Connection
Torque
Grounding
22 Nm (195 lb-in)
AC connection
18 Nm (160 lb-in)
DC connection
44 Nm (390 lb-in)