Table 9: Extract of BAT Error Codes (continued)
Code
Error Description
Corrective Action
157
OV-Protection_/_Filter_Fuses
Check OV-Protection
158
Insulation Error
Check Insulation
159
Voltage_Measurement_Failed
Check voltage measurement
161
Inverter_HW_Error_L1
Check Powerstack
162
Inverter_HW_Error_L2
Check Powerstack
163
Inverter_HW_Error_L3
Check Powerstack
164
Port_Idc_error
Check Idc-Sensor connection
169
Precharge_DC-Link
Check Precharge
171
Grid_rotation
Check grid rotation
172
Switch_on_condition failed
Check Grid voltage / frequency
174
Frequency_error
Check frequency
175
Island_Grid_detected
Check Grid voltage
All corrective action shall be carried out by one ore more qualified
individuals
8.1.1 BAT Error Codes 11-21
The covers are connected with the PE conductor to the cabinet.
Corrective action:
1.
Clean
the cooling air inlet and outlet (Figure 9, Figure 10).
2.
Check
the insect mesh (cooling air inlet and outlet) for pollutions.
If insect mesh is polluted,
remove
insect mesh on back and top of
housing.
3.
Remove
cooling air cover and insect mesh on top of housing.
4.
Clean
insect mesh.
5.
Fix
insect meshes.
8.1.2 BAT Error Codes 22-29
Corrective action:
1.
Check
if the miniature circuit breaker (-F4) is in position
I
.
If the miniature circuit breaker (-F4) is in position
0
,
switch
the
miniature circuit breaker (-F4) in position
I
.
2.
Check
that the ambient temperature is within the specified limits (Table
15).
8.1.3 BAT Error Codes 66-68, 71-73, 76-78, 116-118, 121-123, 126-128, 175
Corrective action:
1.
Ensure
that the motor protecting switch (-F31) is in position
I
.
2.
Measure
the AC voltage.
3.
Check
if the values are within the specified limits.
The values can be seen in the
Interface Description
.
Summary of Contents for BATD0100-ES-1-480-1