Burner Control CBR
c) Control and Operating Faults
Fault Display
Fault / Cause
Check / Resolution
F1
flashing
Bus fault
The TWI bus cable (service interface) is
blocked by a defective bus client (e.g.
defective Vision Box)
F2
flashing
Display fault (internal)
The connected display is invalid
F3
flashing
Password fault
Note: Access to device configuration
levels protected by dedicated passwords
Incorrect password entered or password
not confirmed by pressing reset button.
F4
Reset fault
Prolonged reset signal present (> 10
seconds) or signal is already present when
connecting power
F5
flashing
Input fault
An attempt was made to overwrite a non
changeable parameter.
Button combination locked
F7
flashing
Burner (CBR) locked out
(A burner may be turned off in this
fashion)
The CBR is locked out
Comfort Configuration “0” or parameter
10 (manual mode) is set to “3”
For example after long operation in
manual mode.
Comfort Configuration “0” or parameter
10 must be set to “0” (automatic mode) or
to manual mode (“1” or “2”)
F8
flashing
Configuration error
Parameters 65 and 90 have colliding
settings.
F9
flashing
Profibus fault
The connection with the Profibus master
interrupted; Profibus IC defective or
missing