P. 13 / 25
Burner Control CBR
Manual Operation CBR
Please follow all applicable safety regulations. Depicted configurations may differ from the actual scope of delivery, procedures however,
remain principally the same.
For service adjustments, emissions testing und failure diagnosis the burner can be operated in manual
mode.
Prerequisites:
The power supply must be connected phase correct and all contacts of the process line permissives /safety
limits are closed, so that power (same potential) is present at the „safety chain“ terminal of the CBR.
The following adjustments can be made via Comfort Configuration „Step 0“ or Parameter 10:
•
0 – Automatic operation
•
1 – Manual mode: Air purge
•
2 – Manual mode: Heating
•
3 – lock out control box (locked)
These selections require a password (operator password)
Entering Password (Operator):
Manual Mode Air Purge:
Air purge ON
Air purge OFF