P. 10 / 25
Burner Control CBR
Tab.3: Status byte EB2 – signal reference (CBR
→
Master):
(In dependence of Bit 1 (EB0) „burner fault“, either the operating status (State) may be analyzed at
„0“ or the fault code may be analyzed at „1“
Byte
(decimal)
Byte
(HEX)
Display
CBR
State
Text
0
Fxx
0
Fault – Fault Code
1
01
00
1
Pre-purge
2
02
d3
2
Safety chain interrupted – self resetting
3
03
01
3
Test R1 (Relay SHK is tested for 5 seconds)
4
04
1
4
Watchdog loading phase
5
05
A0
5
Flame: waiting for heat demand
6
06
A1
6
Flame: false flame signal
7
07
A1
7
Flame: idle check air delta-p switch 1
8
08
H1
8
Manual mode pause 1
9
09
A1
9
Flame : air pre-purge
10
0A
A1
10
Flame: Ignition on
11
0B
A1
11
Flame: Ignition off
12
0C
A1
12
Flame: Flame supervision
13
0D
A2
13
Flame: minimum time start mode
14
0E
A2
14
Flame: Start mode (max 24 h)
15
0F
H2
15
Manual mode pause 2
16
10
A3
16
Flame: minimum time flame mode
17
11
A3/H3
17
Flame: Flame operation / manual mode pause
18
12
H4
18
Manual mode pause 3
19
13
A4
19
Flame: Post purge
20
14
A4
20
Flame: Post combustion duration
21
15
A4
21
Flame: Minimum pause flame mode
22
16
b0
22
FLOX: waiting for heat demand
23
17
b1
23
FLOX: idle check air delta-p switch 1
24
18
b2
24
FLOX: air pre-purge
25
19
b2
25
FLOX: Start FLOX mode
26
1A
b2
26
FLOX: Minimum time FLOX mode
27
1B
H6
27
Manual mode: Pause 4
28
1C
b2
28
FLOX: Operation (max. 24h)
29
1D
b4
29
FLOX: Post purge
30
1E
b4
30
FLOX: Minimum pause FLOX mode
31
1F
Pd
31
Air purge: Idle check air delta-p switch 1
32
20
P0
32
Air purge
33
21
d1
33
Excess temperature burner head
34
22
C0
34
Cooling (cooling air)
35
23
d2
35
Start and flame mode not released
36
24
H5
36
Manual mode: Pause 5
37
25
d4
37
False flame during restart attempt