Product Information
Greenstar Condensfit II – 6 721 819 755 (2019/12)
4
2
Product Information
Intended use
These instructions cover the following flue accessory kits:
• 7 733 601 221 - Horizontal flue kit 60/100 - High rise
• 7 716 191 086 - Plume management system
The 60/100mm flue kit accessories are intended for use with Worcester
Greenstar wall mounted condensing gas appliances.
The flue elbow has an in-built 3° angle giving the flue assembly the rise
from the appliance to ensure the condensate flows back to the
appliance. The flue terminal plume re-direct allows to change the
discharge direction of the plume exhaust. The terminal plume redirect
can also be replaced with the plume management system to discharge
away from the property to a more suitable location.
2.1
Standard package
• 60/100mm Horizontal fixed flue kit - High rise
– Part No.: 7 733 601 221
Fig. 3
Standard package contents
1. Instructions
2. Fixed flue assembly
– Inner wall seal (white)
– Outer wall seal (black)
– Fixed flue (860mm)
3. Flue elbow
4. Screw pack
– Securing screws x 2
5. Grease sachet
2.2
60/100mm flue accessories
Table 2
* High level horizontal flue adaptor is required when connecting the
horizontal flue kit for higher level flue discharge compared to the
standard 90° flue elbow.
Fig. 4
Accessories
3
Pre-installation
3.1
Pre-Installation
WARNING:
Flue joints and cut flue sections
Possible carbon monoxide leakage
▶ Secure all joints with the screws supplied in the appropriate flue kit
and accessory.
The sole purpose of the screws is to ensure that a correctly
assembled joint cannot become separated due to external
influences. They are not intended to provide any mechanical strength
or support.
▶ A hole must be pre-drilled in the outer flue using a 3mm drill-bit
wherever a screw is be used to secure a joint. The joint may not be
properly secured if the outer flue is not pre-drilled. Ensure you do not
accidentally drill into the inner flue.
▶ When cutting sections, always take care not to damage the tubes,
chamfer the edge of the inner tube and remove any burrs from both
tube sections to assist in ease of connection and to prevent seal
damage.
1
High level horizontal flue adaptor *
7 719 002 432
2
220mm extension
7 716 191 133
3
1,000mm extension
7 716 191 083
4
2,000mm extension
7 716 191 172
5
90° elbow
7 716 191 084
6
45° elbow (set of 2)
7 716 191 085
7
Support bracket kit
7 716 191 177
8
Support bracket kit (set of 6)
7 716 191 178
1
2
4
0010031751-001
5
3
1
2
3
4
5
6
7
x 6
8
0010013464-001