TECHNICAL INFORMATION
6 720 641 467 (2010/01)
47
_”_\Heating season
_”_\_”_\Heating season limit
K
18 °C
_”_\_”_\Delay
K
4 h
_”_\_”_\Direct start limit
K
10 °C
_”_\Heating, maximum operating time at
hot water demand
K
20 min.
_”_\Shut down protection, change over
hot water to heating
I/S
300 s
_”_\Compressor working area settings
_”_\_”_\Delay after temporary stop
I/S
30 min.
Hot water (T3)
_”_\Extra hot water
_”_\_”_\Number of hours
K
0
_”_\_”_\Stop temperature
K
65 °C
_”_\Hot water peak
_”_\_”_\Interval
K
0 days
_”_\_”_\Start time
K
03:00
_”_\_”_\Stop temperature
I/S
65.0 °C
_”_\Hot water temperature
_”_\_”_\_”_\T3 Start temperature
I/S
52 °C
_”_\_”_\_”_\T8 Stop temperature
I/S
59 °C
_”_\_”_\_”_\T9 Stop temperature
I/S
54 °C
_”_\_”_\Additional heat only?
_”_\_”_\_”_\T3 Stop temperature
I/S
56 °C
_”_\_”_\_”_\T3 Hysteresis
I/S
1.0 °C
_”_\_”_\Hot water, maximum operating
time at heating demand
K
30 min.
_”_\Time control hot water
K
Off
_”_\Hot water additional heat
_”_\_”_\T3 Start value offset
I/S
5.0 °C
_”_\_”_\T3 Hysteresis
I/S
2.0 °C
Temperatures
_”_\Correct sensor
I/S
.0
Defrost settings
_”_\T12 - T11 settings (6-11 kW)
_”_\_”_\Time for reached temperature dif-
ference
I/S
60 s
_”_\_”_\Difference at +10 °C
I/S
12 °C
_”_\_”_\Difference at 0 °C
I/S
8 °C
_”_\_”_\Difference at -10 °C
I/S
6 °C
_”_\T12 - T11 settings (12-17 kW)
Advanced menu
Level
F-value
Tab. 8
_”_\_”_\Time for reached temperature dif-
ference
I/S
60 s
_”_\_”_\Difference at +10 °C
I/S
8 °C
_”_\_”_\Difference at 0 °C
I/S
4 °C
_”_\_”_\Differential at -10 °C
I/S
2 °C
_”_\Maximum outdoor temperature
I/S
13 °C
_”_\T11 Maximum temperature
I/S
20 °C
_”_\Maximum time
I/S
15 min.
_”_\Delay after compressor start
I/S
10 min.
_”_\Minimum time between defrosts
I/S
30 min.
_”_\Compressor pressure equalisation
time
I/S
60 s
_”_\4-way valve pressure equalisation time
I/S
0 s
_”_\Forced defrost
I/S
No
_”_\Heating cable time after defrost
I/S
15 min.
_”_\Fan defrost
_”_\_”_\Fan defrost interval
I/S
1 ggr
_”_\_”_\Fan defrost time
I/S
1.0 min.
_”_\_”_\Temperature limit
I/S
-5 °C
Timers
Additional heat settings
_”_\Start delay
I/S
60 min.
_”_\Time control additional heat
I/S
Off
_”_\Additional heat options
_”_\_”_\Additional heat only?
I/S
No
_”_\_”_\Block additional heat?
I/S
No
_”_\Electric additional heat settings
_”_\_”_\Power guard
_”_\_”_\_”_\Power guard
I/S
Off
_”_\_”_\_”_\Supply voltage
I/S
400 V
_”_\_”_\_”_\Main fuse
I/S
16 A
_”_\_”_\_”_\Display/Correction of Current
transformer
I/S
.0 A
_”_\_”_\_”_\Current margin
I/S
0.5 A
_”_\_”_\_”_\Time from tripped power guard
to possible reconnection
I/S
60 s
_”_\_”_\Connection capacity (electric element)
_”_\_”_\_”_\State total output
I/S
13.5 kW
_”_\_”_\_”_\Compressor mode, output limi-
tation
I/S
4.5/6.75 kW
_”_\_”_\_”_\Additional heat only, output
limitation
I/S
9.0/13.5 kW
Advanced menu
Level
F-value
Tab. 8