Woodward
Technical Manual WIC1
48
DOK-TD-WIC1E, Rev. L
6.7.3 Switching points for the short-circuit step
DIP 1-1
OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON
DIP 1-2
OFF OFF ON
ON OFF OFF ON
ON OFF OFF ON
ON OFF OFF ON
ON
DIP 1-3
OFF OFF OFF OFF ON
ON
ON
ON OFF OFF OFF OFF ON
ON
ON
ON
DIP 1-4
OFF OFF OFF OFF OFF OFF OFF OFF ON
ON
ON
ON
ON
ON
ON
ON
HEX switch I>>
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
Setting xIs
1
2
3
4
5
6
7
8
9
10
12
14
16
18
20 EXIT
Is = Hex „0“
0.32 0.64 0.96 1.28 1.60 1.92 2.24 2.56 2.88 3.20 3.84 4.48 5.12 5.76 6.40
-
Is = Hex „1“
0.36 0.72 1.08 1.44 1.80 2.16 2.52 2.88 3.24 3.60 4.32 5.04 5.76 6.48 7.20
-
Is =
Hex „2“
0.40 0.80 1.20 1.60 2.00 2.40 2.80 3.20 3.60 4.00 4.80 5.60 6.40 7.20 8.00
-
Is = Hex „3“
0.44 0.88 1.32 1.76 2.20 2.64 3.08 3.52 3.96 4.40 5.28 6.16 7.04 7.92 8.80
-
Is = Hex „4“
0.48 0.96 1.44 1.92 2.40 2.88 3.36 3.84 4.32 4.80 5.76 6.72 7.68 8.64 9.60
-
Is = Hex „5“
0.52 1.04 1.56 2.08 2.60 3.12 3.64 4.16 4.68 5.20 6.24 7.28 8.32 9.36 10.40
-
Is = Hex „6“
0.56 1.12 1.68 2.24 2.80 3.36 3.92 4.48 5.04 5.60 6.72 7.84 8.96 10.08 11.20
-
Is = Hex „7“
0.60 1.20 1.80 2.40 3.00 3.60 4.20 4.80 5.40 6.00 7.20 8.40 9.60 10.80 12.00
-
Is = Hex „8“
0.64 1.28 1.92 2.56 3.20 3.84 4.48 5.12 5.76 6.40 7.68 8.96 10.24 11.52 12.80
-
Is = Hex „9“
0.68 1.36 2.04 2.72 3.40 4.08 4.76 5.44 6.12 6.80 8.16 9.52 10.88 12.24 13.60
-
Is = Hex „A“
0.72 1.44 2.16 2.88 3.60 4.32 5.04 5.76 6.48 7.20 8.64 10.08 11.52 12.96 14.40
-
Is = Hex „B“
0.80 1.60 2.40 3.20 4.00 4.80 5.60 6.40 7.20 8.00 9.60 11.20 12.80 14.40 16.00
-
Is = Hex „C“
0.88 1.76 2.64 3.52 4.40 5.28 6.16 7.04 7.92 8.80 10.56 12.32 14.08 15.84 17.60
-
Is =
Hex „D“
0.96 1.92 2.88 3.84 4.80 5.76 6.72 7.68 8.64 9.60 11.52 13.44 15.36 17.28 19.20
-
Is = Hex „E“
1.04 2.08 3.12 4.16 5.20 6.24 7.28 8.32 9.36 10.40 12.48 14.56 16.64 18.72 20.80
-
Is = Hex „F“
1.12 2.24 3.36 4.48 5.60 6.72 7.84 8.96 10.08 11.20 13.44 15.68 17.92 20.16 22.40
-
Table 6.4: Test current via CD winding with the I>> step and the different Is setting values