Manual 37187A
SYNCONpanel - Transportable Remote Synchronizing Panel
Automatic Mode Configuration
Power On Mode:
STOP
Start in mode:
STOP, MANUAL, AUTOMATIC, as before
STOP
............The unit is in STOP operating mode after applying battery voltage.
MANUAL
....The unit is in MANUAL operating mode after applying battery volt-
age.
AUTOMATIC
The unit is in AUTOMATIC operating mode after applying bat-
tery voltage.
as before
.......The unit is in the same operating mode after applying battery voltage
as it was before disconnecting the battery voltage.
Note:
The operating mode may be changed with the terminals 126, 127, and 128.
Interchange Mode
in Manual ON
Interchange mode in manual
ON/OFF
OFF
..............Interchange mode (enabled by the DI at terminal 126) may also be
performed in AUTOMATIC operating mode.
ON
................Interchange mode (enabled by the DI at terminal 126) may
only
be
performed in AUTOMATIC operating mode.
Breaker Configuration
Breaker logic:
--------PARALLEL
Breaker logic
see below
The control automatically controls the two breakers (MCB and GCB). Up to five
(5) breaker logic modes may be selected. These are: EXTERNAL, PARALLEL,
OPEN TRANSIT, CLOSED TRANSIT and INTERCHANGE.
For mobile systems the parallel logic is required.
NOTE
In case of transfer and mains parallel operation mode, phase matching is required. The SYNCON Panel
will not operate, if this parameter is disabled.
Phase matching
ON
Phase matching
ON/OFF
ON
................Synchronization will be performed with phase matching.
OFF
..............Synchronization will be performed with slightly positive slip.
Phase matching
gain 00
Phase matching gain
1 to 36
The phase matching effect on the frequency control may be affected with this gain
factor.
Phase matching
df start 00,0Hz
Phase matching df start
0,02 to 0,25 Hz
Phase matching will only be enabled if the frequency difference of the voltages to
be synchronized is below the value configured here.
Detection Mains
connected < 00°
Mains connection detection (angle)
1 to 15°
If the phase angle between busbar and mains is below the angle configured here for
at least the time configured in the next parameter, the unit detects the connection be-
tween busbar and mains and indicates this with the message "Mains connected".
Page 22/27
© Woodward