Manual 37187A
SYNCONpanel - Transportable Remote Synchronizing Panel
Page 12/27
© Woodward
The following is valid for free operating mode selection at the GCP:
STOP:
Genset stops with cool down or remains stopped. If necessary, the load will be taken off of the
genset and the GCB will be opened.
MANUAL:
Genset may be started and stopped manually. The generator breaker may be closed and opened
using the manual keys.
AUTOMATIC:
The genset will be started and the GCB will be closed if remote control has been activated.
TEST:
Not possible; if transfer operation is selected during TEST operation, an automatic change to
MANUAL operating mode will be performed.
The set points for frequency and voltage or real power and power factor may either be modified using the arrow
keys at the unit, via the digital inputs, or using the SYNCON Panel.
Only the set points, the control of which is currently active, may be modified via the Dis.
Switch Position Peak Load Operation "Internal"
The GCP operating modes are enabled:
STOP:
Genset stops with cool down or remains stopped. If necessary, the load will be taken off of the
genset and the GCB will be opened.
MANUAL:
Genset may be started and stopped manually.
The generator breaker may be closed and opened using the manual keys. After closing the
GCB, real and reactive power are controlled.
AUTOMATIC:
The genset will be started and the GCB will be synchronized if remote control has been acti-
vated. After closing the GCB, real and reactive power are controlled. The set real power 1 and
the power factor are stored
"internally"
.
TEST:
The genset will be started. The generator breaker may be closed and opened using the manual
keys.
The set points for real power and power factor may either be modified using the arrow keys at the unit or via the
digital inputs.
Switch Position Peak Load Operation "External"
The functions correspond with the switch position peak load operation "internal" except the difference that the
real power set point is controlled by a 0/4 to 20mA signal or transmitted via an interface.