SYNCONpanel - Transportable Remote Synchronizing Panel
Chapter 6.
Configuration
NOTE
When using the SYNCONpanel together with the GCP-31/
RPQ
+
SC08
, it is not possible to configure and
control the GCP-31/
RPQ
+
SC08
remotely using LeoPC1 via CAN connection. It is required to configure
the unit via LeoPC1 and a DPC connection.
CAUTION
Please note that configuration only should be done in a standstill of the system.
GCP Configuration
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Controller Configuration
Frequency Controller
In case of transfer operation mode, the unit controls frequency and voltage with droop behavior.
For the transfer operation mode, a droop characteristic for the frequency controller is required, otherwise the gen-
erator set would not be able to maintain a stable active power being in parallel with the mains.
Freq.controller
droop 02.0%
Frequency controller droop
0 to 20 %
The internally set value for frequency will be reduced by the configured value,
when the nominal power of the generator is reached.
Setpoint Frequency-Control
Droop (static curve)
80
84
88
92
96
100
104
0
10
20
30
40
50
60
70
80
90
100
110
P
active
in %
f
No
mi
n
a
l
in %
isochron
isotroop
2 %
Figure 6-1: Frequency controller droop characteristic
Page 20/27
© Woodward